Summary of Contents for Voltronic Power Galleon II 3P
Page 1
User Manual 3/3 30K~40K Online UPS Uninterruptible Power Supply System Version: 1.0...
Page 2
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
Table of Contents 1. SAFETY AND EMC INSTRUCTIONS ........................... 1 1-1. T RANSPORTATION AND TORAGE ........................... 1 1-2. P REPARATION ................................1 1-3. I NSTALLATION ................................1 1-4. ONNECTION ARNINGS ............................ 2 1-5. O PERATION ................................... 3 1-6. S TANDARDS ...................................
1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1-1. Transportation and Storage Please transport the UPS system only in the original package to protect against shock and impact.
1-4. Connection Warnings There is no standard backfeed protection inside, please isolate the UPS before working according to this circuit. The isolation device must be able to carry the UPS input current. • This UPS should be connected with TN earthing system •...
1-5. Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads. The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
2. Installation and Operation There are two different types of online UPS: standard and long-run models. Please refer to the following model table. Model Type Model Type 30KL Standard Long-run model model 40KL We also offer optional parallel function for these two types by request. The UPS with parallel function is called as “Parallel model”.
Page 8
Diagram 3: 30K Rear Panel Diagram 4: 40K Rear Panel Diagram 5: 30KL/ 40KL Diagram 6: 30K/40K Input/output Input/Output Terminal Terminal 1. RS-232 communication port 2. USB communication port 3. Emergency power off function connector (EPO connector) 4. Share current port (only available for parallel model)
5. Parallel port (only available for parallel model) 6. Intelligent slot 7. External battery terminal (Only available for long-run model) 8. Line input circuit breaker 9. Maintenance bypass switch (option) 10. Input/Output terminal 11. Output grounding terminal 12. Output terminal: connect to mission-critical loads 13.
Page 10
Terminal block wiring diagram NOTE 1: Make sure that the wires are connected tightly with the terminals. NOTE 2: Please install the output breaker between the output terminal and the load and the breaker should be qualified to leakage current protective function if necessary. Put the cover of terminal block back to the rear panel of the UPS.
2-4. UPS Installation for Parallel System If the UPS is only available for single operation, you may skip this section to the next. 1) Install and wires the UPSs according to the section 2-3. 2) Connect the output wires of each UPS to an output breaker. 3) Connect all output breakers to a major output breaker which will be directly connected to the loads.
3. Operations 3-1. Button Operation Button Function Turn on the UPS: Press and hold the button more than 0.5s until the UPS is on. ON/Enter Button Enter Key: Press this button to confirm the selection in setting menu. Turn off the UPS: Press and hold the button more than 0.5s until the UPS is off. OFF/ESC Button ...
Page 13
LCD Panel: Display Function Backup time information Indicates the battery discharge time in numbers H: hours, M: minutes, S: seconds Fault information Indicates the warning and fault occurs. Indicates the fault codes, and the codes are listed in details in section 3-9. Mute operation Indicates the UPS alarm is disabled.
Battery information Indicates the battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates the battery is not connected. Indicates low battery level and low battery voltage. Input & Battery voltage information Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc: battery voltage, Hz: input frequency 3-3.
Page 15
3. Connect devices to UPS After the UPS is turned on, you can connect devices to the UPS. 1) Turn on the UPS first and then switch on the devices one by one. The LCD panel will display total load level. 2) If it is necessary to connect the UPS to the inductive loads such as a printer, the in-rush current should be calculated carefully in case that it meets the maximum capacity of the UPS because of the high power consumption of this kind of load.
Page 16
NOTE 2: After turning off the UPS, please be aware that the UPS is working in Bypass mode and there is a risk of power loss for connected devices. 2) In Bypass mode, output voltage of the UPS is still existing. In order to cut off the output, switch off the line input breaker (for dual input unit, also switch off the bypass line breaker).
3-5. Parallel Operation (Only for the parallel models) 1. Parallel system initial startup First of all, please make sure all of the UPSs are parallel models with same configuration. 1) Turn on each UPS to AC mode respectively (Refer to section 3-4(1)). Then, measure the inverter output voltage of each phase for each UPS with multimeter.
1) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the load and shut down the system first. 2) Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UPSs will transfer to Bypass mode.
The second line The third line HS.H Hot Standby 3-7. LCD Setting There are three parameters to set up the UPS. Refer to following diagram. Parameter 1 Parameter 1: It’s for program alternatives. Please refer to tables below setting program. Parameter 2 and parameter 3 are the setting options or values for each program.
Page 20
connection. (Normal UPS shutdown means turning off input breaker in bypass/no output mode). 01: Output voltage Interface Setting Parameter 3: Output voltage You may choose the following output voltage in parameter 3: 208: Presents output voltage is 208Vac 220: Presents output voltage is 220Vac 230: Presents output voltage is 230Vac 240: Presents output voltage is 240Vac 02: Output frequency...
Page 21
04: Frequency range for bypass Interface Setting Parameter 2: Set the acceptable low frequency for bypass. 50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 60 Hz system: Setting range is from 56.0Hz to 59.0Hz. The default value is 46.0Hz/56.0Hz. Parameter 3: Set the acceptable high frequency for bypass.
Page 22
09: Maximum battery discharge time setting Interface Setting Parameter 3: 000~999: Set the maximum discharge time from 0 min to 999 min. UPS will shut down to protect battery if the discharge time is due before the battery is under voltage. The default value is 990 min.
Page 23
CHE is default setting. 13: Battery voltage calibration Interface Setting Parameter 2: Select “Add” or “Sub” function to adjust battery voltage to real figure. Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V. 14: Charger voltage adjustment ...
18: Output A voltage calibration Interface Setting Parameter 2: it always shows OP.V as output voltage. Parameter 3: it shows the internal measurement value of the output A voltage, and you can calibrate it by pressing Up or Down according to the measurement from an external voltage meter.
Page 25
Operating mode/status UPS Power On Description When UPS is powered on, it will enter this mode for a few seconds as initializing the CPU and system. LCD display No-output description When bypass voltage/frequency is out of acceptable range or bypass is mode disabled (or forbidden), UPS will enter no-output mode if powering on or turning off the UPS.
Page 26
ECO mode Description When the input voltage is within voltage regulation range and ECO mode is enabled, UPS will bypass voltage to output for energy saving. LCD display...
Page 27
CVCF mode Description When the output frequency is set to “CF”, the inverter will output constant frequency (50 Hz or 60 Hz). In this mode, the UPS will have no bypass output but still charge the battery. LCD display Battery mode Description When the input voltage/frequency is beyond the acceptable range or power failure, UPS will back up the power from battery and alarm will beep every 4...
Page 28
Bypass mode Description When input voltage is within acceptable range and bypass is enabled, turn off the UPS and it will enter Bypass mode. Alarm beeps every two minutes. LCD display Battery Test Description When UPS is in AC mode or CVCF mode, press “Test” key for more than 0.5s. Then, the UPS will beep once and start “Battery Test”.
Page 29
Warning Description If some errors occur in the UPS (but it is still running normally), it will show status one more screen to represent the warning situation. In the warning screen, the icon will be flashing, and it can show up to 3 error codes and each code indicates one error.
3-9. Fault Code Fault code Fault event Icon Fault code Fault event Icon Bus start failure None Inverter relay short circuited None Bus over None Line wiring fault None Bus under None Parallel communication None failure Bus unbalance None Parallel output current None unbalance Converter over current...
3-11.Warning Code Warning code Warning event Warning code Warning event Line situations are different in parallel Battery unconnected system Bypass situations are different in IP Neutral loss parallel system Locked in bypass after overload 3 IP phase abnormal times in 30 minutes Bypass phase abnormal Converter current unbalance Over charge...
4. Trouble Shooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm show on the The AC input power is not Check if input cable firmly front display panel even though the connected well.
Page 33
Symptom Possible cause Remedy Check and correct the input neutral connection. connection is ok and the alarm is still displaying, please refer to the LCD setting section to access neutral loss The input neutral wire is program. If “CHE” is shown in The warning code 02 is shown, the disconnected.
5. Storage and Maintenance 5-1. Storage Before storing, charge the UPS at least 7 hours. Store the UPS with protective cover and upright it in a cool, dry location. During storage, recharge the battery in accordance with the following table: Storage Temperature Recharge Frequency Charging Duration...
6. Specifications MODEL 30KL 40KL CAPACITY* 30KVA / 27KW 40KVA / 36KW INPUT 110 VAC(Ph-N) ± 3 % at 50% Load Low Line Loss 176 VAC(Ph-N) ± 3 % at 100% Load Voltage Low Line Comeback Low Line Loss Voltage + 10V Range 300 VAC(L-N) ±...