Mitsubishi Electric MSZ-G09SV-E1 Service Manual page 48

Split-type, heat pump air conditioners wireless type
Hide thumbs Also See for MSZ-G09SV-E1:
Table of Contents

Advertisement

2. Checking mis-wiring and serial signal error
Outdoor unit does not operate. When the OPERATION INDICATOR lamp (on the left-hand side) flashes on and off
continuously or only once.
Is the self-check function of indoor unit indicated when 52C turns ON
3 minutes later? w1
(
Short circuit of JPG and JPS on the indoor electronic control P.C. board
enables self-check to be displayed in 3 seconds.
Repair wiring.
flashing
Operation
Indicator
w3 Replace the outdoor
electronic control P.C.
board.
w3 · Reactor
· Diode stack
· Power-factor
defective
capacitor
· Smoothing
capacitor
· Fuse
1. Turn OFF the power supply.
2. Turn ON the power supply.
3. Press the EMERGENCY OPERATION switch.
Yes
Is there indoor-outdoor mis-wiring,
poor contact, or wire disconnection?
Turn OFF the power supply and confirm that indoor-
outdoor wiring is correct.
Short-circuit indoor terminal block N and 3.
B
While pressing OPERATE-STOP(ON/ OFF) button on
the remote controller, press the RESET button.
(The above procedure allows OPERATION INDICATOR
lamp to indicate the failure-mode.) w2
Does the OPERATION INDICATOR lamp flash
on and off when OPERATE/STOP(ON/OFF)
button on the remote controller is pressed?
Open-circuit indoor terminal block N and 3,
Check if there is amplitude of 5 to 10V DC between
outdoor terminal block N and 3(for confirmation of serial
signal) and if there is 230V AC between 2 and N.
1. Turn OFF the power supply.
2. Disconnect the connector between the compressor and
the transistor module.
3.Turn ON the power supply.
4. Press the EMERGENCY OPERATION switch.
Is there approx. 325V DC between TAB 63(+) and
Yes
TAB 64(-) on outdoor electronic control P.C.
board?
No
Is there 325V DC between both ends of
smoothing capacitor (C63) in the main circuit?
Is there approx. 230V AC between outdoor
terminal block 2 and N when EMERGENCY
OPERATION switch is pressed 3 minutes after
Yes
turn OFF the power supply and then turn ON
again?
w3 Rectify in-out connecting wire.
Mis-wiring indication
No
A
Yes
Yes
No
Yes
No
48
ON
2.5 seconds OFF
)
Serial signal error indication
w1 If there is any error in
serial signal system, the
mis-wiring indication will
appear by turning the
power OFF and then
turning it back.
w2 Mis-wiring may damage indoor the
electronic control P.C. board during the
operation in the left. Be sure to confirm
the wiring is correct before the operation
starts.
w3 Replace the
No
indoor electronic
control P.C.
(light up or OFF)
board.
w3 Be sure to release the failure-mode
recall function after checking.
Procedure of release of failure-mode
1 Press the EMERGENCY
OPERATION switch.
2 Turn OFF the power supply and
then turn ON again.
3 Press the RESET button on the
remote controller.
A
· Turn OFF inverter-controlled lighting
equipment.
· Turn OFF the power supply and then
turn ON again.
· Press the EMERGENCY
OPERATION switch.
Is mis-wiring or
serial signal error
No
indicated when
52C turns ON 3
minutes later?
Yes
B
ON
· Re-install the
unit away
from light.
· Attach a filter
on receiving
part.