(5) Dew prevention
During COOL or DRY operation with the vane angle at Angle 4 or 5 when the compressor cumulative operation time
exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
(6) SWING MODE (
)
By pressing the SWING button, vertical vane swings horizontally. The remote controller displays "
SWING MODE is cancelled when any of the following operations are performed.
The unit is turned off.
The vertical vane will return to the position just before the swing operation was started.
The operation mode(AUTO, COOL, DRY or HEAT)is changed.
The vertical vane will return to the position just before the swing operation was started.
The SWING button is pressed.
The vertical vane stops at the position when the button is pressed.
(7) Horizontal AIR FLOW (
The vertical vane angle changes as follows by pressing the SWING button.
Press the SWING button.
The vertical vane begins SWING.
When the vertical vane moved to the desired position, press the SWING button again.
The vertical vane stop SWING.
Horizontal AIR FLOW blowing range
About 100-
COOL and DRY
About 150-
(8) Cold air prevention in HEAT operation.
When any of the following conditions occurs in HEAT operation, the vane angle changes to Angle 1 automatically to pre-
vent cold air blowing on users.
Compressor is not operating.
Defrosting is performed.
Indoor coil thermistor RT12 reads 24: or below.
Indoor coil thermistor RT12 temperature is raising from 24°C or below, but it does not exceed 28:.
Indoor coil thermistor RT12 temperature
NOTE: If the temperature of RT12 reads from 24: to 28: at the air conditioner starting, this control works.
)
HEAT
Released
Cold Air Prevention
24:
33
".
Horizontal vane
Set position
Angle 1
28: