Obh629A - Mitsubishi Electric MUZ-SF25VE-E1 Service Manual

Outdoor unit
Hide thumbs Also See for MUZ-SF25VE-E1:
Table of Contents

Advertisement

OPERATING PROCEDURE
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil)
CN722 (Defrost heater) MUZ-SF25/35/42VEH
CN931, CN932 (Fan motor)
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
CN724 (LEV)
(3) Remove the compressor connector (CN61).
(4) Remove the screws fixing the heat sink support and the sep-
arator.
(5) Remove the fixing screws of the terminal block support and
the back panel.
(6) Remove the inverter assembly.
(7) Remove the screw of the earth wire and screw of the termi-
nal block support.
(8) Remove the heat sink support from the P.C. board support.
(9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
4. Removing the discharge temperature thermistor,
defrost thermistor, outdoor heat exchanger tempera-
ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder.
(4) Pull out the defrost thermistor from its holder. (Photo 6)
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.

OBH629A

Photo 3
Screws of the heat sink
support and the separator
Note: As for MUZ-SF25VE(H), the shape of the out-
door heat exchanger is a flat type.
Photo 4 (Inverter assembly)
Heat sink
Heat sink support
Screw of the
inverter P.C. board
Photo 5
Discharge temperature thermistor
46
PHOTOS
Screws of the terminal block
support and the back panel
Screw of the
Terminal block
support
P.C. board
support
Terminal
block
support
Screw of the
earth wire
Screw of the
R.V. coil