Mitsubishi Electric Mr.Slim PUHZ-P100VHA2 Service Manual page 64

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PUHZ-P100VHA2:
Table of Contents

Advertisement

Indication
Outdoor controller board
LED1 (Green) LED2 (Red)
3 blinking 1 blinking
Abnormality of shell thermostat
and discharging temperature (TH4)
2 blinking
Abnormal high pressure (High
pressure switch 63H worked.)
3 blinking
Abnormality of outdoor fan
motor rotational speed
Protection from overheat operation (TH3)
4 blinking
Compressor over current breaking (Start-up locked)
Compressor over current breaking
Abnormality of current sensor (P.B.)
Abnormality of power module
Open/short of discharge thermistor (TH4)
5 blinking
Open/short of outdoor thermistors
(TH3, TH6, TH7 and TH8)
Abnormality of heatsink
6 blinking
temperature
7 blinking
Abnormality of voltage
Abnormality of room temperature thermistor (TH1)
4 blinking
1 blinking
Abnormality of pipe temperature thermistor /Liquid (TH2)
Abnormality of pipe temperature
thermistor/Condenser-Evaporator
Abnormality of drain sensor (DS)
2 blinking
Float switch (FS) connector open
Indoor drain overflow protection
3 blinking
Freezing (cooling)/overheating
(heating) protection
4 blinking
Abnormality of pipe
temperature
1 Error code displayed on remote controller
2 Refer to service manual for indoor unit.
Error
Contents
code
1
U2
U1
U8
Ud
UF
UP
UH
U6
U3
U4
U5
U9
P1
P2
P9
P4
P5
P6
P8
Error
Inspection method
Check if stop valves are open.
Check if connectors (TH4, LEV-A) on outdoor controller board are not
disconnected.
Check if unit fills with specified amount of refrigerant.
Measure resistance values among terminals on indoor valve and outdoor linear
expansion valve using a tester.
Check if indoor/outdoor units have a short cycle on their air ducts.
Check if connector (63H) on outdoor controller board is not disconnected.
Check if heat exchanger and filter are not dirty.
Measure resistance values among terminals on linear expansion valve using a
tester.
Check the outdoor fan motor.
Check if the connector of TH3 on outdoor controller board is disconnected.
Check if stop valves are open.
Check looseness, disconnection, and converse connection of compressor wiring.
Measure resistance values among terminals on compressor using a tester.
Check if outdoor unit has a short cycle on its air duct.
Check if connectors (TH3, TH4, TH6 and TH7) on outdoor controller board and conn-
ector (CN3) on outdoor power board are not disconnected.
Measure resistance value of outdoor thermistors.
Check if indoor/outdoor units have a short cycle on their air ducts.
Measure resistance value of outdoor thermistor(TH8).
Check looseness, disconnection, and converse connection of compressor wiring.
Measure resistance value among terminals on compressor using a tester.
Check the continuity of contactor (52C).
Check if power supply voltage decreases.
Check the wiring of CNAF.
Check if connectors (CN20, CN21, CN29 and CN44) on indoor controller board
are not disconnected.
Measure resistance value of indoor thermistors.
Check if connector (CN31)(CN4F) on indoor controller board is not disconnected.
Measure resistance value of indoor thermistors.
Measure resistance value among terminals on drain-up machine using a tester.
Check if drain-up machine works.
Check drain function.
Check if indoor unit has a short cycle on its air duct.
Check if heat exchanger and filter is not dirty.
Measure resistance value on indoor and outdoor fan motors.
Check if the inside of refrigerant piping is not clogged.
Check if indoor thermistors (TH2 and TH5) are not disconnected from holder.
Check if stop valve is open.
Check converse connection of extension pipe. (on plural units connection)
Check if indoor/outdoor connecting wire is connected correctly. (on plural units
connection)
64
Detailed
reference
page
P.32
P.32
P.34
P.34
P.35
P.34
P.33
P.33
P.33
P.33
P.34
2
2
2
2
2
2