6-4. STANDARD OPERATION DATA
Representative matching
Mode
Capacity
Input
Indoor unit
Phase , Hz
Volts
Input
Amperes
Outdoor unit
Phase , Hz
Volts
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
SHF
BF
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/cm²)
PLA-RP100BA
Cooling
9,400
W
kW
3.12
PLA-RP100BA
1 , 50
230
V
0.14
kW
0.94
A
PUHZ-P100VHA2
PUHZ-P100VHA3
1 , 50
230
V
12.26
A
MPa
2.90
( f/
)
(29.6)
MPa
0.92
( f/
)
(9.4)
72.7
°C
48.6
°C
10.1
°C
5
m
D.B.
27
°C
W.B.
19
°C
D.B.
14.8
°C
D.B.
35
°C
W.B.
24
°C
0.74
0.21
PLA-RP125BA
Cooling
Heating
12,300
11,200
4.09
3.28
PLA-RP125BA
1 , 50
230
0.13
0.15
0.87
1.00

PUHZ-P125VHA2

PUHZ-P125VHA3
1 , 50
230
12.62
17.37
2.57
2.68
(26.2)
(27.3)
0.62
0.86
(6.3)
(8.8)
75.5
67.8
41.4
45.5
0.1
6.8
5
5
20
27
15
19
43.4
13.6
7
35
6
24
0.71
0.18
10
PLA-RP140BA(2)
Heating
Cooling
14,000
13,600
4.11
5.21
PLA-RP140BA(2)
1 , 50
230
0.14
0.16
0.94
1.07

PUHZ-P140VHA2

PUHZ-P140VHA3
1 , 50
230
16.74
22.48
2.56
2.79
(26.1)
(28.5)
0.68
0.79
(6.9)
(8.1)
64.5
72.7
43.4
47.0
1.3
4.4
5
5
20
27
15
19
44.2
12.9
35
7
6
24
0.71
0.14
Heating
16,000
4.98
0.15
1.00
21.31
2.75
(28.1)
0.64
(6.5)
70.8
47.2
1.0
5
20
15
48.0
7
6

Hide quick links: