Trane YSC037E Installation & Operation Manual page 65

Packaged rooftop air conditioners precedent — gas/electric 3 to 10tons – 60 hz
Table of Contents

Advertisement

After approximately 30 seconds, turn the "Mode"
selection switch to the desired mode, i.e. Heat, Cool or
Auto.
Table 16. Fault detection and diagnostic codes
Mixed Air
Outdoor
Temp
Temp
Failures
Sensor
Sensor
Fail
Damper stuck
at Minimum
Damper Stuck
Open
Mixed Sensor
X
Failure
Supply Air
Sensor Failure
Outdoor Air
Temperature
Fail
Power loss to
RTEM
Failed or Power
Loss to
Actuator
Mechanical
Failure of
Actuator
(a) If goes out of range.
Table 17. Low leak economizer sensor values
Resistance
Temp °F
40
41
42
43
44
45
46
47
48
49
50
51
52
53
RT-SVX21P-EN
Primary Fault Codes
Pressure
Economizer
RTEM
Dead band
Actuator
Comm
Fault
Fail
Fail
(If Used)
X
X
X
X
X
Sensor Values Data
(K ohms)
Temp °F
26.097
54
25.383
55
24.690
56
24.018
57
23.367
58
22.736
59
22.132
60
21.530
61
20.953
62
20.396
63
19.854
64
19.330
65
18.821
66
18.327
67
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch "Off" and then "On" .
Temp
Sensor
Airflow
Fail
Sensor Fail
Fail
(If Used)
(If Used)
(a)
(a)
X
X
*
(a)
(a)
X
X
X
X
Resistance
(K ohms)
17.847
17.382
16.930
16.491
16.066
15.654
15.253
14.864
14.486
14.119
13.762
13.416
13.078
12.752
Troubleshooting
Information Code
Space
Unit
Unit Fails
Press Dead
Economizing
to
band Fail
When It
Economize
(If Used)
Should Not
(a)
X
X
(a)
X
X
Temp °F
68
69
70
71
72
73
74
75
76
77
78
79
80
81
Damper
Position %
Indicated
X
X
X
X
X
X
Resistance
(K ohms)
12.435
12.126
11.827
11.535
11.252
10.977
10.709
10.448
10.194
9.949
9.710
9.477
9.250
9.030
65

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ysc060eYhc036eYsc067eYhc037eYhc072eYsc072f ... Show all