The indoor fan motor error has occurred, and the indoor fan does not operate.
Turn OFF the power supply.
Is there any foreign matter that interferes
the rotation of the line fl ow fan?
Yes
Remove the foreign matter and
adjust the line fl ow fan.
Is there 325 VDC
between CN211
and
(–) ?
Replace the indoor electronic control P.C.
board and the indoor terminal P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211
(+) and
(–) while the fan motor is
rotating.
OBH531E
MSZ-GE80VAD
No
Does the voltage between CN211
(+) and
control P.C. board rise to the range
(+)
Yes
of 3 to 6 VDC within 12 seconds after
EMERGENCY OPERATION switch is
pressed?
No
Replace the indoor electronic control
P.C. board.
Replace the indoor fan motor.
MSZ-GE71VAD
Pay enough attention to the high voltage on the fan motor connector CN211.
Turn ON the power supply, wait 5 seconds or more, and then press
EMERGENCY OPERATION switch.
Measure the supply voltage as follows within 12 seconds after EMER-
GENCY OPERATION switch is pressed.
If more than 12 seconds passes, turn OFF the power supply and turn it
ON again, then measure the voltage.
<Indoor electronic control P.C. board>
1. Measure the voltage between CN211
2. Measure the voltage between CN211
If more than 12 seconds passes after EMERGENCY OPERATION switch
is pressed, the voltage measured at 2. above goes 0 V DC although the
indoor P.C. board is normal.
(–) on the indoor electronic
No
Is it unchanged holding
0 or 15 VDC?
No
(Changed)
Yes
(Unchanged)
33
(+) and
(–).
(+) and
(–).
Replace the indoor fan motor.
Yes
Replace the indoor
electronic control P.C.
board.