Failure Mode Recall Function - Mitsubishi Electric MSZ-GE22VA-A1 Service Manual

Split-type air conditioners
Table of Contents

Advertisement

10-2. FAILURE MODE RECALL FUNCTION

Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (10-4.) disappears, the memorized failure details
can be recalled.
This mode is very useful when the unit needs to be repaired for the abnormality which does not recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button (MSZ-
GE22/25/33/35/42/50)/TEMP
ler at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Make sure that the indica-
tors on the LCD screen shown in the right fi gure are all displayed. Then release
the buttons.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set tempera-
ture is displayed) with the remote controller headed towards the indoor unit. 1
Does upper lamp of OPERATION INDICATOR
lamp on the indoor unit blink at the interval of 0.5
seconds?
Blinks: Either indoor or outdoor unit is abnormal.
Beep is emitted at the same timing as the
blinking of upper lamp of OPERATION
INDICATOR lamp. 2
Judgment of indoor/outdoor abnormality
Before blinking, does upper lamp of
OPERATION INDICATOR lamp stay ON for 3
seconds?
Stays ON for 3 seconds (without beep):
The indoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to the
indoor unit failure mode table. (Refer to 10-2.2)
Make sure to check at least two consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
ON
OFF
Repeated cycle
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF
ON
OFF
OBH531E
button (MSZ-GE60/71/80) on the remote control-
Yes
(Blinks)
Yes
The outdoor unit is abnormal.
No
Repair the failure parts.
Blinking at 0.5-
Blinking at 0.5-
second interval
second interval
2.5-second OFF
Beeps
Repeated cycle
Blinking at 0.5-
3-second ON
second interval
No beep
Beeps
Repeated cycle
MSZ-GE22/25/33/35/42/50VA
MSZ-GE35/50VA2
MSZ-GE22/25/35/42/50VAD
Indoor unit is normal.
But the outdoor unit might be abnormal because there are
some abnormalities that cannot be recalled with this way.
No
Check if outdoor unit is abnormal according to the detailed
(OFF)
outdoor unit failure mode recall function.
1 Regardless of normal or abnormal condition, a short beep is
emitted once the signal is received.
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring
to the outdoor unit failure mode table. (Refer to outdoor unit service
manual.)
Make sure to check at least two consecutive blinking cycles. 3
Beeps
Beeps
Repeated cycle
2.5-second OFF
3-second ON
No beep
Repeated cycle
27
MSZ-GE60/71/80VA
MSZ-GE60/71/80VAD
MSZ-GE80VA2
Blinking at 0.5-
second interval
Beeps
Repeated cycle