Specifications - Mitsubishi Electric PRH-P8 Operation Manual

Rooftop unit
Table of Contents

Advertisement

8. Specifications

PRH-P-MYA SERIES
Item
Voltage
Power source
Frequency
Cooling capacity*1
Heating capacity*1
Height
Dimension
Width
Depth
Net weight
Airflow rate
Indoor fan
External static pressure*2
Outdoor fan
Airflow rate
Noise level
Notes: *1 Refer to the product nameplate attached to the unit for the electrical specifications.
*2 Rating conditions (cooling) Indoor: 27°C DB, 19°C WB
*3 Rating conditions (heating) Indoor: 20°C DB
Operating range
Indoor air intake temperature
Maximum
32°C DB, 24°C WB
Cooling
Minimum
21°C DB, 15°C WB
Maximum
Heating
Minimum
Units should be installed by licensed electric contractor accordingly to local code requirement.
Model
PRH-P8MYA
3N~ V
380, 400, 415
Hz
50
kW
20.9
kcal/h
18,000
kW
23.7
kcal/h
20,400
mm
1,715
mm
2,000
mm
961
kg
407
3
m
/min
70
Pa
100
3
m
/min
185
dB(A)
59
Outdoor: 35°C DB, 24°C WB
Outdoor: 7°C DB, 6°C WB
Outdoor air intake temperature
28°C DB
24°C DB, 18°C WB
20°C DB
–11°C DB, –12°C WB
PRH-P10MYA
380, 400, 415
50
26.0
22,400
30.5
26,200
1,715
2,000
961
412
90
100
185
60
43°C DB
–5°C DB
PRH-P16MYA
PRH-P20MYA
380, 400, 415
380, 400, 415
50
50
41.8
52.0
36,000
44,800
47.4
61.0
40,800
52,400
1,735
1,735
2,000
2,000
2,130
2,130
857
872
140
180
200
200
185 × 2
185 × 2
62
63
9