Checking Indoor Unit Electrical Parts; Power Does Not Come On (No Operation) - Hitachi RAS-50FH5 Service Manual

Hide thumbs Also See for RAS-50FH5:
Table of Contents

Advertisement

CHECKING INDOOR UNIT ELECTRICAL PARTS

1. Power does not come on (no operation)

Is DC 35V being generated between
terminals C and D on the terminal
board?
Are control voltages (12V, 5V)
being generated normally?
Y es
Do the air deflectors perform initial
operation when the power supply is
turned on and off?
No
Is the microcomputer reset input
(pin 7 )ÒHiÓ ?
Y es
Is the microcomputer clock signal
10MHz at pin
being
10
11
generated normally?
Y es
Replace the control P .W.B
No
Is AC 220-240V AC being generated
between terminals L and N on the
outdoor unit terminal board?
Is DC 35V being generated between
terminals C and D on the outdoor
unit terminal board?
No
No
Y es
No
No
Perform final operation check.
– 104 –
No
Check AC outlet and breaker, and
repair any defective part.
Y es
Y es
Check the indoor/outdoor unit
connection cable, and correct any
defective section (wrong connection,
incomplete insertion reversed).
Check the outdoor unit power circuit,
and repair the defective section.
Check according to the proper method
for checking the power circuit.
Check the indication P .W.B.
connection cord and light receiving
unit.
Check the reset circuit, and repair
any defective section.
Replace the microcomputer and
oscillator.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rac-50yh5Ras-50yh5

Table of Contents