11-5. Judgment of Trouble by Symptom
11-5-1. Indoor Unit (Including Remote Controller)
(1) Power of indoor unit does not turned on
<Primary check>
1. Is the supply voltage normal?
2. Is the normal voltage provided to the outdoor unit?
3. Is the crossover cable connected properly?
4. Is the fuse (F01) blown?
Turn off power supply once, and
60 second later, turn it on again.
NO
Is OPERATION indicator flashing?
Is fuse (F01)
of indoor control
board blown?
NO
Is voltage
NO
(DC12V or 5V)
indicated on rear of
indoor control
board normal?
NO
Is DC310–340V
Parts of a power supply circuit
supplied between
CN10 1 – 3 ?
YES
• Be sure to disconnect the motor connector CN301 after shut off the power supply, or it will be a cause of
damage of the motor.
(2) Power of indoor unit does not turned on though Indoor P.C. board is replaced
<Confirmation procedure>
Turn on power supply.
Does OPERATION indicator flash?
YES
YES
Is it possible to turn on
NO
power supply by pushing
[START/STOP] button
on remote controller?
YES
Unit operates normally.
YES
Parts (R01, R02, DB01,
C01, C03, IC01 and T101)
are defective.
YES
defective.
NO
Is wired correctly to white and
black lead wires of terminal block?
– 99 –
Does transmission mark
NO
on remote controller flash
normally,and is its signal
transmitted properly?
YES
Does fan
motor connector
between CN301 1 –
3 short-circuit?
NO
Microcomputer
is defective.
NO
YES
Operation
Check Item
Considerable principle cause
Measures
Item by symptoms
Remote controller is defective.
Refer to (5) "Troubleshooting
for remote controller".
YES
Replace main
P.C. board
Replace fan
motor.
Correct wiring.
To item of
"Power supply is not turned on".