Hitachi RAK-25NH5 Service Manual page 81

Room air conditioner indoor unit + outdoor unit
Hide thumbs Also See for RAK-25NH5:
Table of Contents

Advertisement

< Reference >
When operation stop with LD301 blinks 12 times, it may be caused by faulty DC fan motor.
G
In this case, please check CN6 and CN12 connection first. It makes Fan Motor Lock also if those
G
connectors are in misconnection.
DC Fan Motor has broken when 2A Fuse was burned. Please replace both DC Fan Motor and 2A Fuse
G
together.
It will makes "Fan Lock Stop"when something has disturb the Fan rotation by inserting materials into
G
propeller fan or ice has growing inside of outdoor unit by snowing.
It may make "Fan Lock Stop" by strong wind (ex. 17m/sec or above) against the Fan rotation. In this case,
G
unit will be restart again after a while.
In case of "Fan Lock Stop" even though the DC Fan Motor is rotating correctly, the possible casue is
G
Fan Motor problem or PQ102 on board or control board problem. Stop after the Fan motor runs 2 minutes,
Fan Motor may be broken.
< Caution >
Please take care for the electrical shock by high voltage of DC Fan Motor power source which is common
G
with compressor when you are servicing this unit.
You can not confirm the coil and wiring of Motor due to the built in control circuit in Fan Motor.
G
– 92 –

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rac-25nh5Rak-35nh5Rac-35nh5

Table of Contents