Specifications For Electrical Work - Mitsubishi Electric Mr.Slim PUHZ-RP200YHA Service Manual

Outdoor unit split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PUHZ-RP200YHA:
Table of Contents

Advertisement

10

SPECIFICATIONS FOR ELECTRICAL WORK

10-1. FIELD ELECTRICAL WIRING (POWER WIRING SPECIFICATIONS)
Indoor unit model
Phase
Outdoor unit
Frequency & Voltage
Power supply
Max. Permissive System Impedance (" )
Outdoor unit input capacity
Main switch (Breaker)
Outdoor unit power supply
Outdoor unit power supply earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
Outdoor unit L1-N, L2-N, L3-N
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Remote controller-Indoor unit
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Max. 80 m Total Ma including all indoor/ indoor connection is 80 m.
· Use one cable for S1 and S2 and another for S3 as shown in the picture.
*3. A 10 m wire is attached in the remote controller accessory.
*4. The voltage are NOT against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord.
(Design 245 IEC 57)
3. Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.
The earth wire should also be thicker than the power supply cord so that it can stand any surge of electricity when trouble occurs.
.
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between
power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals
when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
1:1 system
Outdoor
unit
L
1
L
2
B
C
Unit
L
3
power
N
supply
Indoor/outdoor
unit connection
cable
S1
B Earth leakage breaker
S2
C wiring circuit breaker or
S3
isolating switch
*1
*2
*3
*4
*4
*4
S1
380/400/415V 50Hz
Three phase (4 wires)
Isolator (Switch)
S1
A-Control
Outdoor
S2
Unit
S3
Indoor
unit
1
Remote
controller
2
S1
S2
S3
RP200, 250
3N~(3ph 4-wires), 50Hz,
380-400-415V
0.25
32A
4 o Min. 6
1 o Min. 6
Cable length 50 m : 3 o 4 (Polar) / Cable length 80 m : 3 o 6 (Polar)
1 o Min. 2.5
2 o 0.69 (Non-polar)
AC 220-230-240V
AC 220-230-240V
DC24V
DC12V
S2
S3
3 poles isolator (Switch)
Synchronized twin and triple system Electrical wiring
• Synchronized twin
Outdoor
Outdoor
unit
unit
L
1
L
2
B
C
L
Unit
3
power
N
supply
S1
B Earth leakage breaker
S2
C wiring circuit breaker or
S3
isolating switch
• Synchronized triple
Outdoor
unit
L
L
Unit
B
C
L
power
N
supply
S1
B Earth leakage breaker
S2
C wiring circuit breaker or
S3
isolating switch
15
S1
A-Control
Indoor
S2
Unit
S3
Indoor
unit
1
Remote
controller
2
Indoor/outdoor
unit connection
cable
S1
S2
S3
Indoor
1
unit
2
1
Remote
3
controller
2
Indoor/outdoor
connection cable
S1
S2
S3
Indoor
unit
1
2
S1
S2
S3
Indoor
Indoor
unit
unit
1
1
2
2
S1
S1
S2
S2
S3
S3