The unit of pressure has been charged to MPa based on international SI system.
The converesion factor is : 1(MPa)=10.2(kgf/cm
6-5. ADJUSTING THE AMOUNT OF REFRIGERANT
<Table 2>
permitted
Outdoor unit
pipe length
RP200
120m or less
RP250
Calculate the additional charge amount based on the following procedure.
If the calculation results in an amount that is smaller than the "Additional charge amount for 70m," perform the additional charge using the amount shown
in "Additional charge amount for 70m."
Main piping:
Amount of additional
Liquid line size
=
charge [kg]
[12.7 over all length [m]
o 0.12 [kg/m]
Additional charge amount
RP200 3.6 kg
for 70 m
RP250 4.8 kg
2
)
At time of shipping
(kg)
30 m and less
10.5
No additional
charge necessary
10.5
Main piping:
Liquid line size
+
[9.52 overall length [m]
o 0.09 [kg/m]
PEH-RP200MYA
Cooling
PEH-RP200MYA
V
kW
A
PUHZ-RP200YHA
PUHZ-RP200YHA
V
A
10.63
MPa
2.81
(kgf/cm
2
)
(28.7)
MPa
0.92
(kgf/cm
2
)
(9.4)
˚C
73.0
˚C
47.1
12.2
˚C
m
5
D.B.
˚C
27
W.B.
˚C
19
D.B.
˚C
14.7
D.B.
˚C
35
W.B.
˚C
24
0.75
0.18
Amount of additional refrigerant charge (kg)
31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less