VENT CONNECTION TO THE WATER HEATER

Bend both the corrugated pipes toward the fl ue connection
on the water heater. Pull and connect the inner corrugated
pipe to the water heater's fl ue tube reducer with hi-temp
red silicone (included) and gear clamp. Make sure this
connection is tight and leak proof (see Figure 24).
*The sealant between the inner corrugated pipe and water
heater's fl ue tube reducer must be hi-temp red silicone
or other material suitable for 600°F continuous service.
Note: If you are using the vent restricter plate, the inner
vent pipe is to go over the side legs and down the stops.
SMOOTH,
EASY CURVE
RESTRICTER
PLATE STOP
CUTAWAY TO
SHOW DETAILS
Figure 24
Apply hi-temp red silicone (included) around the collar on
air manifold box. Pull the outer corrugated pipe all the way
on to collar and secure with the gear clamp. Pull the free
end of the corrugated pipe past the gear clamp and secure
with one sheet metal screw (see Figure 25).
FLUE TUBE
REDUCER
APPLY
SILICONE
GEAR
CLAMP
www. hotwater .com
SMOOTH,
EASY CURVE
APPLY
SILICONE
TO AIRBOX
BEFORE
ATTACHING
PIPING
SECURE
WITH A
SHEET METAL
SCREW
Figure 25

OFFSET VENT ARRANGEMENT

Where a straight vent arrangement is impossible, a
horizontal 90° maximum bend can be made. Use the
water heater casing outer diameter as a template to form
the corrugated tube.
SMOOTH,
EASY CURVE
Figure 26
Figure 27
Note: To ensure good exhaust gas fl ow, bend vent piping
using a smooth, easy curve as shown in Figure 24 thru
Figure 26. Do not use reverse or compound curves as
shown in Figure 27.
GEAR
CLAMP
90°
MAXIMUM
BEND