For Right Rear Piping - LG LS-J0762YL Service Manual

Room air conditioner
Hide thumbs Also See for LS-J0762YL:
Table of Contents

Advertisement

Tighten the flare nut with a wrench.
Torque wrench
Indoor unit tubing
Outside diameter
mm
Ø6.35
Ø9.52
Ø12.7
When extending the drain hose at the indoor unit,
install the drain pipe.
Drain pipe
Adhesive
6. Wrap the insulation material around the connect-
ing portion.
Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there is no gap.
Plastic bands Insulation material
Spanner (fixed)
Flare nut
Connection pipe
Torque
kg . m
inch
1/4
1.8
3/8
4.2
1/2
5.5
Indoor unit drain hose
Vinyl tape(narrow)
Wrap the area which accommodates the rear piping
housing section with vinyl tape.
Connection
pipe
Vinyl tape
(wide)
Connecting cable
Vinyl tape(narrow)
Bundle the piping and drain hose together by wrap-
ping them with vinyl tape over the range within which
they fit into the rear piping housing section.
Pipe
Drain hose

For right rear piping

1. Route the indoor tubing and the drain hose to the
required piping hole position.
2. Insert the piping, drain hose and the connecting
cable into the piping hole.
-29-
Indoor
unit pipe
Wrap with vinyl tape
Pipe
Wrap with vinyl tape
Vinyl tape(wide)
Connecting cable
Drain pipe