Continuous Fan Operation; Cooling Sequence Of Operation - Carrier Comfort 50ES-A Installation Instructions Manual

Comfortt 13 seer single-packaged air conditioner system with puron (r-410a) refrigerant single and three phase 2-5 nominal tons (sizes 24-60)
Hide thumbs Also See for Comfort 50ES-A:
Table of Contents

Advertisement

HIGH
QC5
KZ
R13 C8
07
09
0L0
08
ALO
C9
C4
QIL
Z2
06
04
A7
R9
D5 D3
C7
JW5
R3 R5 R6
R2
QCB
Y
SSTZ-8
P1
W3
Fig. 12 - - Interface Fan Board (IFB)
Single Speed Cooling With Higher Electric Heat Speed
This unit can also be configured to operate with single speed
cooling and a higher speed for an accessory electric heater.
1. Using Fig. 12, move the two pin DEHUM jumper from the
"STD" position to the "DEHUM" position.
2. See Table 2 for minimum airflow for electric heat operation.
Add electric heater and filter pressure drop to duct system
static pressure to determine total external static pressure.
3. Select speed tap from Table 4 that will achieve required
airflow from Table 2.
4. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 3 for color coding).
5. Connect the desired speed tap wire to the "HIGH" terminal
on the interface fan board (IFB).
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit component
damage or improper operation.
To use this mode, a speed connection must be made on the
"HIGH" terminal that meets or exceeds the minimum
airflow found in Table 2.
LOW
COM
QC4
QC3
KL
DCR
QCR
C
R11
Q1
D2
QC1
Q3
AL2
RL
G1
01
G2
AB A15
F1
C0
Z1
U1
R4
RL4
C3
JWZ
P2
JW3
P4
R W2 Y
C
W3 W3 W2 W2 C
JW4
Y2
Y1
W2
G
C R
DH
Y
A09059
Table 3 – Color Coding for Indoor Fan Motor Leads
Black = High Speed
Orange = Med- -High Speed
Red = Med Speed
Pink = Med- -Low Speed
Blue = Low Speed
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect electrical power to the unit and install lockout
tag before changing blower speed.

Continuous Fan Operation

When the DEHUM feature is not used, the continuous fan speed
will be the same as cooling fan speed. When the DEHUM feature
is used, the continuous fan speed will operate on Low when the D2
control lead is energized, or High when the D2 lead is not
energized.

COOLING SEQUENCE OF OPERATION

With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO position, the cooling sequence of
operation is as follows:
When the room temperature rises to a point that is slightly above
the cooling control setting of the thermostat, the thermostat
completes the circuit between thermostat terminal R to terminals Y
and G. These completed circuits through the thermostat connect
contactor coil (C) (through unit wire Y) and time delay relay
(TDR) (through unit wire G) across the 24- -V secondary of
transformer (TRAN).
The normally open contacts of energized contactor (C) close and
complete the circuit through compressor motor (COMP) to
condenser (outdoor) fan motor (OFM). Both motors start instantly.
A set of normally open contacts on the interface fan board (IFB)
are closed which energizes a circuit to the indoor fan motor (IFB).
NOTE: Once the compressor has started and then has stopped, it
should not be started again until 5 minutes have elapsed.
The cooling cycle remains on until the room temperature drops to a
point that is slightly below the cooling control setting of the room
thermostat. At this point, the thermostat breaks the circuit between
thermostat terminal R to terminals Y and G. These open circuits
deenergize contactor coil C and IFB. The condenser and
compressor motors stop. After a 90- -second delay, the blower
motor stops. The unit is in a standby condition, waiting for the next
call for cooling from the room thermostat.
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents