Condensate Connections - Worcester GREENSTAR 24i junior Instruction Manual

Wall hung rsf gas fired condensing combination boiler for sealed central heating systems and mains fed domestic hot water
Table of Contents

Advertisement

SUMP
BLANKING CAP
DISCHARGE
HOSE
DISCHARGE
HOSE
WALL FRAME
CONNECTOR
28
CONDENSATE CONNECTION
SUMP
CONNECTION
SYPHON
4
DRAINAGE CAP
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior
CONDENSATE CONNECTION
CONDENSATE CONNECTION:
Never terminate or discharge into any open
source, including; sink, bath, shower, bidet,
1
toilet etc.
Note: Any external condensate pipework
should be protected with weather
resistant insulation to help prevent
freezing.
• Ensure that the condensate drain is 22mm
diameter plastic pipe. It must fall at least
50mm per metre towards the outlet.
Note: Do not use lubricants or sealing
compounds.
1 Remove the sump blanking cap from the
sump.
2 Fill syphon with 200 to 250 millilitres of
water.
3
Note: Pull the fan lead and ignition cable out of
the way when fitting the syphon to
ensure that they are are not trapped
by the syphon assembly or discharge
hose.
3 To fit the syphon assembly:
Note: Do not use solvents, adhesive or
lubricant when pushing the pipe
onto the rubber connector.
Slide the assembly onto the sump
connection.
Push the syphon onto the sump
assembly, until the lug on the sump is fully
engaged with the slot on the back of the
syphon assembly.
4 Push the discharge hose, onto the
wall frame connector, until fully engaged.
Maintenance
There is no need to remove the Syphon
Assembly for cleaning.
To drain debris from the syphon, during the
annual service, release the clips and remove
the drainage cap from the bottom of the
syphon.
Empty the debris and condensate from the
syphon into a suitable container.
Re-fit the drainage cap to bottom of the
syphon.