AirTap ATI50 Owner's Manual & Installation Instructions page 13

Hybrid water heater
Hide thumbs Also See for ATI50:

Advertisement

OPERATING INSTRUCTIONS
A. GETTING STARTED
How do I turn on the unit?
IMPORTANT:
Before attempting to turn on the unit, please ensure the following:
1. Unit is connected to a dedicated 240V/60Hz single phase power outlet rated for at least 30 amperes. Confirm that
this power outlet is not being shared with another appliance. Confirm that the unit is grounded.
2. Condensate drains (primary and overflow) are piped correctly to drain condensate.
3. Unit is COMPLETELY filled with water and there are NO LEAKAGES from any connecting port/valve. To check if the
tank is full:
a. Ensure drain valve is shut tightly
b. Open cold water inlet valve to fill the tank
c. Open hot water faucets slowly to allow air in the tank and piping to vent out
d. Smooth, undisrupted flow of water from the faucets indicates that the tank is full.
You are now ready to turn the unit on by pressing the 'ON' button in the Control Panel.
When the unit is off, the 'OFF' indicator in the control panel will be lighted. Please ensure the unit remains off until the
tank is full with water.
Turning the unit on when the tank is not completely full with water will cause water temperature to rise quickly and
trigger an alarm. If the alarm is triggered, turn the unit off and re-check that the tank is completely filled with water.
B. OPERATING MODES
Which mode is right for me? How can I change the current mode?
The unit is preset to Auto mode. You may choose any of the following three modes depending on your hot water usage
and operating environment:
AUTO MODE (recommended): Auto mode runs the unit as a 'hybrid' to combine the efficiency of a heat pump with the
high hot water delivery rate of an electric water heater. Average household hot water demand can be met by the heat
pump alone. However, if hot water demand were to rise above normal levels, the electric element is triggered to
supplement the heating provided by the heat pump.
ECON MODE: Econ mode is the most energy efficient mode in the unit. In this mode, electric element is deactivated
and water is heated exclusively by the heat pump to maximize energy efficiency. While the Econ mode is factory set to
run anytime during the day to meet hot water demand, users have the option to configure the timer feature to allow
the unit to run during chosen time periods only (users may select up to 3 operating time periods in a 24 hour cycle).
This mode allows users to take advantage of off-peak power tariff rates.
HEATER MODE: In the Heater mode, heat pump is de-activated and water is heated by electric element only. Please
note that Heater mode will automatically revert to Auto mode within 48 hours of the Heater mode being activated (48
hours is the default setting – users may choose any duration from 12 to 999 hours). Users may select Heater mode to
temporarily deactivate the heat pump and stop cold air exhaust and/or operate the unit at a lower noise level.
Press MODE button to select or switch between any of the three modes.