Guide Specifications - Carrier WEATHERMASTER 50HJQ004-016 Product Data

Single-package rooftop standard and high efficiency units 3 to 15 nominal tons
Hide thumbs Also See for WEATHERMASTER 50HJQ004-016:
Table of Contents

Advertisement

Guide specifications — 50TFQ004-012 (cont)
K. Motors:
1. Compressor motors shall be cooled by refriger-
ant passing through motor windings and shall
have line break thermal and current overload
protection.
2. Indoor blower motor shall have permanently
lubricated bearings and inherent automatic-
reset thermal overload protection.
3. Totally enclosed outdoor-fan motor shall have
permanently lubricated bearings, and inherent
automatic-reset thermal overload protection.
L. Special Features:
Certain features are not applicable when the fea-
tures designated by * are specified. For assistance in
amending the specifications, your local Carrier Sales
Office should be contacted.
* 1. Carrier PremierLink™ Controls:
a. Shall be available as a factory-installed or as
a field-installed accessory.
b. Shall work with Carrier Comfort Network®
(CCN) and ComfortVIEW™ software.
c. Shall be compatible with ComfortLink™
controllers.
d. Shall be ASHRAE 62-99 compliant.
e. Shall accept a CO
space — Demand Control Ventilation (DCV)
Ready.
f. Shall have baud communication rate of
38.4K or faster.
g. Shall be Internet Ready.
h. Shall include an integrated economizer
controller.
2. Roof Curbs:
a. Formed galvanized steel with wood nailer
strip and capable of supporting entire unit
weight.
b. Allows for installing and securing ductwork
to curb prior to mounting unit on the curb.
*
3. Integrated Economizers:
a. Integrated integral modulating type capable
of simultaneous economizer and compressor
operation. During economizer operation, up
to two compressors on sizes 008-014 will
operate.
b. Available as a factory-installed option in ver-
tical supply/return configuration only. (Avail-
able as a field-installed accessory for
dedicated horizontal and/or vertical supply
return configurations.)
c. Includes all hardware and controls to provide
cooling with outdoor air.
d. Equipped with low-leakage dampers, not to
exceed 2% leakage at 1 in. wg pressure
differential.
e. Capable of introducing up to 100% outdoor
air.
78
sensor in the conditioned
2
f. EconoMi$er IV and EconoMi$er2 shall be
equipped with a barometric relief damper
capable of relieving up to 100% return air.
g. Designed to close damper(s) during loss-of-
power situations with spring return built into
motor.
h. Dry bulb outdoor-air temperature sensor
shall be provided as standard. Outdoor air
sensor set point is adjustable and shall range
from 40 to 100 F. For the EconoMi$er IV,
the return air sensor, indoor enthalpy sensor,
and outdoor enthalpy sensor shall be pro-
vided as field-installed accessories to provide
enthalpy control, differential enthalpy con-
trol, and differential dry bulb temperature
control. For the EconoMi$er2, the enthalpy,
differential temperature (adjustable), and dif-
ferential enthalpy control shall be provided
as field-installed accessories.
i. The EconoMi$er IV and EconoMi$er2 shall
have a gear-driven parallel blade design.
j. EconoMi$er IV microprocessor control shall
provide control of internal building pressure
through its accessory power exhaust func-
tion. Factory set at 100%, with a range of
0% to 100%.
k. EconoMi$er2 shall be capable of control
from a 4 to 20 mA signal through optional
4 to 20 mA design without microprocessor
control (required for PremierLink™ or third
party control interface).
l. EconoMi$er IV Microprocessor Occupied
Minimum Damper Position Setting main-
tains the minimum airflow into the building
during occupied period providing design
ventilation rate for full occupancy (damper
position during heating). A remote potenti-
ometer may be used to override the set
point.
m. EconoMi$er IV Microprocessor Unoccupied
Minimum Damper Position Setting — The
EconoMi$er IV damper shall be completely
closed when the unit is in the occupied
mode.
n. EconoMi$er IV Microprocessor IAQ/DCV
Maximum Damper Position Setting — Set-
ting the maximum position of the damper
prevents the introduction of large amounts
of hot or cold air into the space. This posi-
tion is intended to satisfy the base minimum
ventilation rate.
o. EconoMi$er IV Microprocessor IAQ/DCV
control modulates the outdoor-air damper to
provide ventilation based on the optional 2
to 10 vdc CO
p. Compressor lockout sensor (opens at 35 F,
closes at 50 F).
q. Actuator shall be direct coupled to economizer
gear, eliminating linkage arms and rods.
905
sensor input.