Model Number Nomenclature - Carrier AQUAZONE 50PEC09-18 Product Data

Water source heat pumps console unit with puron (r-410a) refrigerant 3/4 to 1 1/2 nominal tons
Table of Contents

Advertisement

Model number nomenclature

Aquazone™ Water Source Heat Pump
Console Unit with Puron® (R-410A)
Refrigerant
LEGEND
DDC — Direct Digital Control
*See table for autoflow regulator sizing.
†Right and left hand orientation is determined by looking at front of unit.
**Sizes 09-12 only.
NOTES:
1. Standard 60 Hz unit controls are ETL listed.
2. Complete C controllers take 50-va transformers. Deluxe D controllers take
75-va transformers. All DDC controllers take 75-va transformers.
3. The 50PEC09-15 unit cabinets are 48 in. with ½ in. water connections. The
50PEC18 unit cabinet is 54 in. with ¾ in. water connections.
4
**
AUTOFLOW REGULATOR SIZING
50PEC
2.25 gpm/ton
UNIT SIZE
09
2.0
12
2.5
15
3.0
18
3.5
a50-8312
NRTL/C
3.0 gpm/ton
2.5
3.0
3.5
4.0
As an ENERGY STAR® Part-
ner, Carrier Corporation has
determined that this product
meets
the
ENERGY
STAR
guidelines for energy efficiency.

Advertisement

Table of Contents
loading

Table of Contents