Typical Wiring Schematic; Electrical Data - Carrier 58PAV Product Data

High-efficiency induced-combustion upflow input capacities: 45,000 thru 155,000 btuh
Table of Contents

Advertisement

Typical wiring schematic

THREE-WIRE
BLK
BLK
WHT
WHT
GND
AUXILIARY
115-VOLT FIELD-
J-BOX
SUPPLIED
FUSED
DISCONNECT

Electrical data

UNIT SIZE
UNIT VOLTS — HERTZ — PHASE
MINIMUM WIRE SIZE
MAXIMUM WIRE LENGTH (Ft)*
MAXIMUM UNIT AMPS
OPERATING VOLTAGE RANGE (Min—Max)†
MAX FUSE SIZE OR HACR-TYPE CKT BKR (Amps)‡
TRANSFORMER (24v)
EXTERNAL CONTROL POWER AVAILABLE Heating
AIR CONDITIONING BLOWER RELAY
* Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.
† Permissible limits of the voltage range at which the unit will operate satisfactorily.
‡ Time-delay fuse is recommended.
NOTE 2
W
C
FIVE
WIRE
HEATING-
ONLY
W
R
GND
G
C
NOTE 1
CONTROL
Y
BOX
24-VOLT
TERMINAL
BLOCK
NOTES:
FURNACE
045-08 045-12 070-08 070-12 090-14 090-16 111-12 111-16 111-20 135-16 135-20 155-20
14
47
6.0
15
Cooling
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
THERMOSTAT
R
G
Y
TERMINALS
CONDENSING
UNIT
TWO
WIRE
1.
Connect Y-terminal as shown for proper operation.
2.
Some thermostats require a "C" terminal connection as shown.
3.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
115 — 60 — 1
14
14
14
14
34
47
32
31
8.3
5.9
8.7
9.0
15
15
15
15
FIELD-SUPPLIED
FUSED DISCONNECT
208/230- OR
460-VOLT
THREE
PHASE
208/230-
VOLT
SINGLE
PHASE
GND
14
14
14
12
27
35
28
31
10.4
8.0
10.1
14.4
104 — 127
15
15
15
20
40va
12va
35va
Standard
A95241
14
12
12
28
33
31
10.1
13.3
14.0
15
20
20
7