Electrical data

50RHC,RVC
VOLTS-PHASE
UNIT SIZE
60 Hz
208/230-1
006*
265-1
208/230-1
009
265-1
208/230-1
012
265-1
208/230-1
018
265-1
208/230-1
265-1
024
208/230-3
460-3
208/230-1
265-1
030
208/230-3
460-3
208/230-1
265-1
036
208/230-3
460-3
208/230-1
208/230-3
041†
460-3
575-3
208/230-1
208/230-3
042
460-3
575-3
208/230-1
208/230-3
048
460-3
575-3
208/230-1
208/230-3
060
460-3
575-3
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA
— Locked Rotor Amps
RLA
— Rated Load Amps
*Size 006 available in 50RHR unit only.
†Size 041 available in 50RVC unit only.
NOTES:
1. HACR circuit breaker in U.S.A. only.
2. All fuses Class RK-5.
3. The modulating reheat option is only available on 50RVC018-036
and 50RVC042-060 units.
4. All 460 v units require a four (4) wire power supply with neutral.
Reheat pump is rated 265 v and is wired between one hot leg and
neutral.
5. The 50RVC048 and 50RCV060 460 v units reheat pump is prelim-
inary data pending UL approval.
30
50RHC,RVC ELECTRICAL DATA
COMPRESSOR
VOLTAGE
MIN/MAX
RLA
LRA
197/254
2.9
17.7
239/292
2.5
15.0
197/254
3.9
22.2
239/292
3.3
18.8
197/254
5.3
27.9
239/292
4.2
22.2
197/254
8.6
49.0
239/292
8.1
44.0
197/254
9.8
56.0
239/292
9.1
55.0
197/254
6.7
51.0
414/506
3.5
25.0
197/254
11.2
61.0
239/292
10.0
58.0
197/254
6.9
55.0
414/506
3.6
28.0
197/254
15.4
82.0
239/292
14.4
83.0
197/254
9.6
70.0
414/506
4.9
33.0
197/254
16.2
96.0
197/254
10.3
75.0
414/506
4.3
40.0
518/633
4.3
34.0
197/254
17.1
105.0
197/254
10.7
85.0
414/506
5.3
42.0
518/633
3.7
31.0
197/254
18.3
102.0
197/254
12.6
91.0
414/506
5.7
42.0
518/633
4.7
39.0
197/254
25.6
170.0
197/254
14.7
124.0
414/506
7.4
59.6
518/633
5.9
49.4
STANDARD UNITS
Fan Motor
Total Unit
Min Circuit
FLA
FLA
AMP
0.40
3.3
4.1
0.35
2.8
3.5
0.80
4.7
5.7
0.70
4.0
4.8
0.80
6.1
7.5
0.70
4.9
6.0
1.00
9.6
11.7
0.86
8.9
11.0
1.50
11.3
13.8
1.30
10.4
12.7
1.50
8.2
9.9
0.76
4.2
5.1
3.00
14.2
16.9
2.70
12.7
15.2
3.00
9.9
11.7
1.70
5.3
6.2
1.80
17.2
21.1
2.00
16.4
20.0
1.80
11.4
13.8
1.24
6.1
7.4
3.00
19.2
23.2
3.00
13.3
15.8
1.70
6.0
7.1
1.40
5.7
6.8
3.00
20.1
24.3
3.00
13.7
16.4
1.70
7.0
8.3
1.50
5.2
6.1
3.40
21.7
26.3
3.40
16.0
19.2
1.80
7.5
8.9
1.40
6.1
7.2
4.30
29.9
36.4
4.30
19.0
22.7
2.50
9.9
11.8
1.90
7.8
9.3
MODULATING
REHEAT UNITS
Reheat
Total
Max
Pump
Unit
Fuse/HACR
FLA
FLA
15
15
15
15
15
15
20
0.80
10.4
15
0.70
9.6
20
0.80
12.1
20
0.70
11.1
15
0.80
9.0
15
0.70
4.9
25
0.80
15.0
25
0.70
13.4
15
0.80
10.7
15
0.70
6.0
35
0.80
18.0
30
0.70
17.1
20
0.80
12.2
15
0.70
6.8
35
25
15
15
40
0.80
20.9
25
0.80
14.5
15
0.70
7.7
15
40
1.07
22.7
30
1.07
17.1
15
1.00
8.5
15
60
1.07
31.0
35
1.07
20.1
15
1.00
10.9
15
Min
Max
Circ
Fuse/
AMP
HACR
12.5
20
11.7
15
14.6
20
13.4
20
10.7
15
5.8
15
17.7
25
15.9
25
12.5
15
6.9
15
21.9
35
20.7
35
14.6
20
8.1
15
25.1
40
17.2
25
9.0
15
27.3
45
20.3
30
9.9
15
37.4
60
23.8
35
12.8
20