Bryant LEGACY T2-PAC Installation Instructions Manual page 14

Legacy series thermostats
Hide thumbs Also See for LEGACY T2-PAC:
Table of Contents

Advertisement

Option 10 - - Reversing valve
This selection is only available on heat pump systems. "O" terminal can be
configured to be energized in either heating mode or in cooling mode, depending
on heat pump operation. "O" is used to describe a heat pump system that
energizes its reversing valve in cooling. "B" is used to describe a heat pump
system that energizeS its reversing valve in heating.
H — Reversing valve output (O/W2/B) is energized when HEAT mode is
selected.
C — Reversing valve output (O/W2/B) is energized when COOL mode is
selected.
Default is C.
Option 11 - - Minimum Deadband Between Heating And Cooling
Selections:
01 through 06 — Default is 02.
Sets the minimum allowable number of degrees between heating and cooling
setpoints. One setpoint will "push" the other to maintain this difference.
Option 12 - - Smart Recovery (programmable model only)
Selections:
OF, 30, 60, 90 — Default is 90.
Smart Recovery OF means setpoints change immediately at a program schedule
change. Thirty, 60, or 90 selects the number of minutes recovery starts before
programmed recovery time. Recovery takes place smoothly during the selected
recovery time, ending at the recovery time and temperature which is
programmed. If the setpoint is changed during smart recovery, the smart
recovery is cancelled and the new setpoint is effective immediately. Not available
with non- -programmable thermostats.
14

Advertisement

Table of Contents
loading

This manual is also suitable for:

Legacy t2-nacLegacy t2-phpLegacy t2-nhpA07047A07046

Table of Contents