Table 1. Installer Setup (Continued).
Installer
Installer
Setup
Setup
Number
Name
0670
Keypad
Lockout
0680
Temperature
Control Heat
0685
Recovery
Heat Ramp
Rate
62-0266
Default
Setting
All Settings
0
0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Fully Locked
2
1—Less Aggressive
2—Standard
3—More Aggressive
5
0-20° F/hour
(-18- -7° C)
8
Notes
Unlocked: All
functions
accessible.
Partial 1: Locks all
but Holiday,
Override, and Up/
Down.
Partial 2: Locks all
but Holiday and
Override.
Full: Entire
interface locked/
non-functional.
Only shown if
system has heat
stages.
Only integral gains
affected. Affects
control operation in
all control regimes
(not just recovery
or setpoint
change).
More Aggressive
stops signal prior to
reaching the
setpoint. (For use
with oversized
equipment.)
Only shown if
system has heat
stages.
0 disables ramped
recovery (step
setpoint change at
period start time).