Electrical Data; Electrical Data - LG LC247HV Engineering Manual

Single-zone four-way ceiling-cassette system
Hide thumbs Also See for LC247HV:
Table of Contents

Advertisement

eleCtriCal Data

electrical Data

Table 3: Electrical Data.
Nominal
Unit Model No.
Tons
1.5
LUU187HV
2
LUU247HV
3
LUU367HV
3.5
LUU427HV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
10 | Four-Way caSSette
Voltage
Hertz Voltage
Range
(Min. to Max.)
60
208 - 230
187 - 253
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Compressor
MCA
MOP
Quantity
18.1
30
1
24.5
40
1
Condenser Fan Motor(s)
Compressor
Motor RLA
Condenser
Condenser Fan
(Cooling)
Fan Quantity.
13.5
1
18.0
2
Motor FLA
0.6
0.6 x 2