Clearance Requirements when Different Obstacles are Present (Unit: Inch), continued.
Obstacles above and on the air intake side. Obstacles above, on the air intake side,
Obstacle just on the
air discharge side.
Where there are obstacles on both suction
Where there are obstacles on both suction
and discharge sides (discharge side obstacle
and discharge sides (discharge side obstacle
is higher than the outdoor unit).
is higher than the outdoor unit).
PlaCement ConSiderationS
and on both left and right sides
Obstacles above and on the
Where there are obstacles above, and on both
Where there are obstacles above, and on both
suction and discharge sides (discharge side obstacle
suction and discharge sides (discharge side obstacle
is higher than the outdoor unit).
is higher than the outdoor unit).
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
air discharge side.
L
L
H
H
A
A
outdoor unit
Table 28: Ratio among H, A, and L.
L
0 < L ≤ 1/2 H
29-1/32 inches
L
H
1/2 H < L
39-3/8 inches
H
L
<
Set Stand as: L ≤ H
If a stand is necessary, it should be contained (not open
frame) to prevent the discharge air from short cycling.
duct (HIgH StatIc) | 47