Single-zone ceiling-concealed duct (high static) heat pump systems 2 and 3 tons (24,000 btu/h) & (36,000 btu/h)
Hide thumbs Also See for LH247HV:
Table of Contents

Advertisement

PlaCement ConSiderationS
outdoor unit
Tie-Downs / Wind Restraints and Lightening Protection
The strength of the Ceiling-Concealed Duct (High Static) system
outdoor unit frame is adequate to be used with field-provided wind
restraint tie-downs.
Tie-Downs / Wind Restraints
• The strength of the roof must be checked before installing the
outdoor units.
• If the installation site is prone to high winds or earthquakes, when
installing on the wall or roof, securely anchor the mounting base
using a field-provided tie-down configuration approved by a local
professional engineer.
• The overall tie-down configuration must be approved by a local
professional engineer. Always refer to local code when using a
wind restraint system.
Lightening Protection
• To protect the outdoor unit from lightning, it should be placed within
the specified lightning safety zone.
Table 26: Safety Zone Specifications.
Building Height (feet)
Protection Angle (˚)
• Power cable and communication cable should be installed five (5)
feet away from lightning rod.
• A high-resistance ground system should be included to protect
against induced lightning or indirect strike.
general mounting
Securely attach the outdoor unit to a condenser pad, base rails, or other mounting platform
that is securely anchored to the ground or building structure. The underlying structure or
foundation must be designed to support the weight of the unit, and avoid placing the outdoor
unit in a low lying area where water may accumulate.
Attaching the Outdoor Unit to the Bracket
When installing the outdoor unit on a wall or roof top, anchor the mounting base securely
using nails or wire with regard to wind and earthquake or vibration.
Refer to installation manual, and follow the applicable local code for clearance, mounting,
anchor, and vibration attenuation requirements.
• All referenced materials are to be field-supplied.
• Images are not to scale.
44 | duct (HIgH StatIc)
66
98
148
197
55
45
35
25
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 26: Lightening Protection Diagram.
Lightning rod
Lightning rod
If the building does not include lightning protection, the outdoor unit
may be damaged from a lightening strike. Inform the customer of
this possibility in advance.
Figure 27: Bracket Mounting.
Protection Angle (25˚~55˚)
5 feet
1.5m
Safe zone
Ground