Wiring; Restrict Wiring To Shaded Area; Wiring Connections; Wiring Diagram In A Single Transformer System With Gas Heat - Honeywell T8400B Installation Instructions Manual

Electronic thermostats
Table of Contents

Advertisement

Wiring

IMPORTANT
Use an 18-gauge maximum wire for wiring the
T8400B,C and T8401C Thermostats.
All wiring must comply with local electrical codes and
ordinances. Disconnect the power supply to prevent
electrical shock or equipment damage.
NOTE: To ensure proper mounting of thermostat,
restrict all wiring to the shaded area on the left
side of the terminals. See Fig. 3.
KEEP WIRING IN
ALTERNATE MOUNTING
SHADED AREA
SCREW HOLE
W
Y
R
C
WIRING ENTRANCE HOLE
MOUNTING
SCREW HOLE
Fig. 3. Restrict wiring to shaded area.
The shape of the terminals permits insertion of straight
or wraparound wiring connections; either method is
acceptable. See Fig. 4.
W
Fig. 4. Wiring connections.
MOUNTING
SCREW
HOLE
G
ALTERNATE
MOUNTING
SCREW HOLE
Y
G
FOR WRAPAROUND
STRIP 7/16 IN. (11 MM)
R
FOR STRAIGHT INSERTION
STRIP 5/16 IN. (8 MM)
C
TERMINAL SCREW
T8400B,C; T8401C ELECTRONIC THERMOSTATS
The T8400B Thermostat is powered through the heating
system control. The T8400B is adaptable to most 2-wire
and 3-wire 18 to 30 Vac heating systems. Refer to Fig. 5
and 6 for typical wiring hookups.
1
L1
(HOT)
L2
1
Fig. 5. T8400B heat-only wiring diagram in a single
transformer system with gas heat.
1
L1
M11023
(HOT)
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
Fig. 6. T8400B heat-only wiring diagram in a single
transformer system with gas heat.
The T8400C Thermostat is powered through the
heating/cooling system controls and is adaptable to
most 4-wire, 18 to 30 Vac heating-cooling systems.
The T8401C Thermostat is powered directly from the
system transformer and is adaptable to most 5-wire, 18
to 30 Vac heating-cooling systems. Refer to Fig. 7 and 8
for typical wiring hookups.
M11232
3
T8400B
W
R
24V
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
T8400B
W
G
R
24V
HEAT
PRIMARY
CONTROL
M10974
FAN
HEATING
RELAY
PRIMARY
CONTROL
M10973
69-1494–1