Front Panel Menus
Set HW (Hardware) Configuration
If you added an EBM to the UPS, you must select the amp/hour rating
through the Battery Setup option. The hardware configuration options
are:
:
:
Set Language
The front panel is translated into eight languages: Danish, Dutch,
English, French, German, Spanish, Italian, and Japanese. An asterisk (*)
shows the current language used for the front panel menus.
Set Alarm Horn
Use the Set Alarm Horn option to enable or disable the audible alarm.
Set Password
Use the Set Password option to modify the user password for the
System Setup Menu. Use
values. Use
To save the password, press
long.
Set Sync Range
This option is for viewing only and displays the frequency tolerance:
:
:
40
Load Control (reserved for future use)
Battery Setup - select 5 Ah for each EBM.
*
and
to move to the next character in the password.
p
3 Hz for Normal mode
p
5 Hz for Extended mode (+5/–3 @ 50 Hz)
?
+
and
to scroll through the character
. The password must be six characters