Powerware 5140 User Manual page 12

6000 va; 6000w
Hide thumbs Also See for 5140:
Table of Contents

Advertisement

Safety Warnings
4
:
Input overcurrent protection and disconnect switch must be provided by others.
:
To reduce the risk of fire, connect only to a circuit provided with 40 amperes
maximum branch circuit overcurrent protection in accordance with the National
Electrical Code, ANSI/NFPA 70 and Canadian Electrical Code, C22.1.
:
Batteries can present a risk of electrical shock or burn from high short circuit
current. Observe proper precautions. Servicing should be performed by qualified
service personnel knowledgeable of batteries and required precautions. Keep
unauthorized personnel away from batteries.
:
Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
:
This UPS contains its own energy source (batteries). The UPS output may carry live
voltage even when the UPS is not connected to an AC supply.
:
Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
:
To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient
temperature must not exceed 40
excessive humidity (95% max).
C A U T I O N
C (104
F). Do not operate near water or
Powerware
5140 User's Guide
®
:
www.powerware.com