Toshiba TOSVERT VF-S11 Specifications page 7

Transistor inverter
Hide thumbs Also See for TOSVERT VF-S11:

Advertisement

Extended parameters 1
2005 Ver.112/113
Parameters for setting functions that cannot be fulfilled by basic parameters.
Input terminal functions assignment parameters
A variety of functions can be given to various compatible input terminals by assigning the function numbers
for the parameter in the table below.
Title
Function
Adjustment range
Always active function selection 1
0-75 (No function)
Always-active function selection 2
0-75 (ST)
Input terminal selection 1 (F)
0-75 (F)
Input terminal selection 2 (R)
0-75 (R)
Input terminal selection 3 (RES)
0-75 (RES)
Input terminal selection 4 (S1)
0-75 (SS1)
Input terminal selection 5 (S2)
0-75 (SS2)
Input terminal selection 6 (S3)
0-75 (SS3)
Input terminal selection 7 (VIB)
5-17 (SS4)
Input terminal selection 8 (VIA)
5-17 (AD2)
input terminal functions list
Function
Function
Function
Function
No.
No.
0
No function
38
Frequency command forced switching
1
Standby
39
No.2 Switching of V/F setting
2
Forward run command
40
Combination of No. 5, 39 and 61
3
Reverse run command
41
Frequency UP signal input from external contacts
4
Jog run mode
42
Frequency DOWN signal input from external contacts
5
Acceleration/deceleration 2 pattern selection
43
Frequency UP/DOWN cancellation signal input from external contacts
6
Preset-speed command 1
44
Combination of No. 10 and 43
7
Preset-speed command 2
45
Inversion of No. 11
8
Preset-speed command 3
46
Thermal trip stop signal input from external device
9
Preset-speed command 4
47
Inversion of No. 46
10
Reset command
48
Forced switching from remote to local control
11
Trip stop command from external input device
49
Operation holding (stop of 3-wire operation)
12
Switching of command mode and frequency setting mode
50
Forced switching of command mode and terminal board command
13
DC braking command
51
Display cancellation of the cumulative power amount (kWh)
14
PID control prohibited
52
Forced operation (factory configuration required)
15
Permission of parameter editing
53
Fire-speed control
16
Combination of No. 1 and 10
54
Coast stop (gate off)
17
Combination of No. 1 and 12
55
Inversion of No. 10
18
Combination of No. 2 and 4
56
Combination of No. 1 and 2
19
Combination of No. 3 and 4
57
Combination of No. 1 and 3
20
Combination of No. 2 and 5
58
Acceleration/deceleration 3 selection
21
Combination of No. 3 and 5
59
Combination of No. 2 and 58
22
Combination of No. 2 and 6
60
Combination of No. 3 and 58
23
Combination of No. 3 and 6
61
Forced switching of stall prevention level 2
24
Combination of No. 2 and 7
62
Holding of RY-RC terminal output
25
Combination of No. 3 and 7
63
Holding of OUT-NO terminal output
26
Combination of No. 2 and 8
64
Cancellation (clearing) of operation command from panel
27
Combination of No. 3 and 8
65
PID control integral value clear
28
Combination of No. 2 and 9
66
Combination of No. 1, 2 and 6
29
Combination of No. 3 and 9
67
Combination of No. 1, 3 and 6
30
Combination of No. 2, 5 and 6
68
Combination of No. 1, 2 and 7
31
Combination of No. 3, 5 and 6
69
Combination of No. 1, 3 and 7
32
Combination of No. 2, 5 and 7
70
Combination of No. 1, 2 and 8
33
Combination of No. 3, 5 and 7
71
Combination of No. 1, 3 and 8
34
Combination of No. 2, 5 and 8
72
Combination of No. 1, 2 and 9
35
Combination of No. 3, 5 and 8
73
Combination of No. 1, 3 and 9
36
Combination of No. 2, 5 and 9
74
Combination of No. 1, 2 and 4
37
Combination of No. 3, 5 and 9
75
Combination of No. 1, 3 and 4
Output terminal functions assignment parameters
A variety of functions can be given to various compatible output terminals by assigning the function
numbers for the parameter in the table below.
Title
Function
Adjustment range
Output terminal selection 1A (RY-RC)
0-255 (LOW)
Output terminal selection 2A (OUT-NO)
0-255 (RCH)
Output terminal selection 3 (FL)
0-255 (FL)
Output terminal selection 1B (RY-RC)
0-255 (always ON)
Output terminal selection 2B (OUT-NO)
0-255 (always ON)
Output terminal logic selection (RY-RC, OUT-NO)
0, 1, 2, 3
Output terminal functions list
Function No.
Function
Function No.
Function
0/1
Frequency lower limit
30/31
Ready for operation (including ST/RUN)
2/3
Frequency upper limit
32/33
Ready for operation (excluding ST/RUN)
4/5
Low-speed detection signal
34/35
Frequency VIB selection
6/7
completion of acceleration/deceleration signal
36/37
Fault signal (put out also at the time of a retry)
8/9
Designated frequency attainment signal
38/39
Specified data output
Failure signal (trip output)
Specified data output 2
10/11
40/41
12/13
Over-torque detection
42/43
Cumulative operation time alarm
14/15
Start/Stop
44/45
Parts replacement alarm
16/17
OL pre-alarm
46/47
Braking sequence output
Braking resistor overload pre-alarm
F terminal input signal
18/19
48/49
Over-torque detection pre-alarm
Inversion of R terminal input signal
20/21
50/51
22/23
pre-alarm
52/53
Signal in accordance of frequency command
24/25
Small-current detection
54/55
Undervoltage detection
Significant failure
Invalid settings, always OFF (ignored)
26/27
56-253
Insignificant failure
Always OFF
28/29
254
Always ON
255
Note) For functions 0 to 55, even numbers are true logic and odd numbers are false logic.
Carrier frequency parameters
Set parameters related to deep carrier frequency motor noise.
Title
Function
Adjustment range
Default setting
PWM carrier frequency
2.0-16.0 (kHz)
0
Random mode
0: Invalid, 1: Automatic setting
1
Carrier frequency control mode selection
0, 1, 2, 3
2
3
Frequency command (terminal block) specialized parameters
10
Set characteristics if input frequency instruction is input from terminal block.
6
Title
Function
Adjustment range
7
8
Frequency priority selection
0 1
9
VIA input point 1 setting
0 100 (%)
0 500 (Hz)
5
VIA input point 1 frequency
VIA input point 2 setting
0 100 (%)
VIA input point 2 frequency
0 500 (Hz)
0 6 (same as
)
Frequency setting mode selection 2
VIB input point 1 setting
0 100 (%)
VIB input point 1 frequency
0 500 (Hz)
VIB input point 2 setting
0 100 (%)
VIB input point 2 frequency
0 500 (Hz)
VIA input bias
VIA input gain
VIB input bias
VIB input gain
Input/output terminal function parameters
Set specific values for functions such as low-speed/signal output and speed arrival signal output.
Title
Function
Adjustment range
Low-speed signal output frequency
0
(Hz)
Speed reach setting frequency
0
(Hz)
Speed reach detection band
0
(Hz)
Analog/logic input function selection
0 4
(VIA/VIB terminal)
Frequency command agreement
0
(Hz)
detection range
Protection parameters
Set protection operations, trip output and alarm output settings etc.
Title
Function
Adjustment range
Auto-restart control selection
0, 1, 2, 3, 4
Regenerative power ride-through control (Deceleration stop)
0,1, 2
Retry selection (number of times)
0: Invalid, 1-10 (times)
Overvoltage limit operation (Slowdown stop mode selection)
0, 1, 2, 3
Supply voltage correction (limitation of output voltage)
0, 1, 2, 3
Stall prevention level 1
10-199 (%/A), 200 (Invalid)
Inverter trip retention selection
0, 1
Emergency stop selection
0, 1, 2
Emergency DC braking time
0 20 (s)
Output phase failure detection mode selection
0, 1, 2, 3, 4, 5
Motor 150%-overload time limit
10-2400 (s)
Input phase failure detection mode selection
0: Invalid, 1: Valid
Torque up parameters
Set to generate high torque to match load or motor.
Title
Function
Adjustment range
Default setting
Auto-tuning
0, 1, 2
4
Slip frequency gain
0-150
(%)
6
Automatic torque boost value
0-30
(%)
10
Motor rated current
0.1-100.0 (A)
255
Motor no-load current
10-90
(%)
255
Motor rated speed
-1
100-32000 (min
)
0
Speed control response coefficient
1-150
Speed control stability coefficient
1-100
Panel display parameters
Set if changing units displayed or various display methods.
Title
Function
Adjustment range
Unit selection
0: %, 1: A (ampere)/V (volt)
Free unit selection
0.00: Invalid, 0.01-200.0
Inclination characteristic
0: Negative inclination,
of free unit display
1: Positive inclination
Free unit display bias
0-
(Hz)
Free step 1 (pressing a panel key once)
0.00: Invalid, 0.01-
(Hz)
Free step 2 (panel display)
0: Invalid, 1-255
Standard monitor display selection
0,1,2,3,4,5,6,7
Canceling of operation command
0: Operation command canceled (cleared),
when standby terminal (ST) is turned off
1: Operation command retained
Panel stop pattern
0: Slowdown stop, 1: Coast stop
* 1: Default values vary depending on the capacity.
Extended parameters 2
Parameters for setting higher functions.
DC Braking parameters
Title
Function
DC braking starting frequency
Default setting
DC braking current
12.0
DC braking time
0
Motor shaft fixing control
1
Multi-stage speed run parameters
Title
Function
Preset-speed operation frequency 8
Default setting
Preset-speed operation frequency 9
Preset-speed operation frequency 10
0
Preset-speed operation frequency 11
0
Preset-speed operation frequency 12
0.0
Preset-speed operation frequency 13
100
Preset-speed operation frequency 14
50 (WP)
Preset-speed operation frequency 15 (Fire-speed)
60 (WN)
1
Power generation braking parameters
0
0.0
Title
Function
Dynamic braking selection
100
Dynamic braking resistance
50 (WP)
Dynamic braking resistor capacity
60 (WN)
No. 2 motor parameters
Title
Function
Base frequency 2
Base frequency voltage 2
Torque boost value 2
Motor electronic-thermal protection level 2
Stall prevention level 2
Default setting
No. 2 and no. 3 acceleration/deceleration time setting parameters
0.0
0.0
Title
Function
2.5
Acceleration time 2
0
Deceleration time 2
Acceleration/deceleration 1 pattern
2.5
Acceleration/deceleration 2 pattern
Acceleration/deceleration 1, 2, 3 selection
Acc/dec 1 and 2 switching frequency
S-pattern lower-limit adjustment amount
S-pattern upper-limit adjustment amount
Acceleration time 3
Default setting
Deceleration time 3
Acceleration/deceleration 3 pattern
0
Acc/dec 2 and 3 switching frequency
0
0
Jog run parameters
2
3
Title
Function
150
Jog run frequency
0
Jog run stopping pattern
0
Panel jog run operation mode
1.0
Jump frequency parameters
0
300
Title
Function
1
Jump frequency 1
Jumping width 1
Jump frequency 2
Jumping width 2
Jump frequency 3
Default setting
Jumping width 3
0
50
Forward/reverse/start frequency parameters
* 1
Title
Function
* 1
Priority selection (Both F-CC and R-CC are ON)
* 1
Starting frequency setting
1710
Operation starting frequency
40
Operation starting frequency hysteresis
20
Time limit for lower-limit frequency operation
Reverse-run prohibition
Analog/pulse train output setting parameters
Default setting
Title
Function
0
Logic output/pulse train output selection (OUT-NO)
Pulse train output function selection (OUT-NO)
0.00
Maximum numbers of pulse train
1
Inclination characteristic of analog output
Meter bias
0.00
0.00
PID control setting parameters
0
0
Title
Function
1
PID control waiting time
PID control
Proportional gain
0
Integral gain
Differential gain
2005 Ver.112/113
Communications functions parameters
Adjustment range
Default setting
Title
Function
0.0-
(Hz)
0.0
Communication rate
0-100 (%/A)
50
Parity
0.0-20.0 (s)
1.0
Inverter number
0: Invalid, 1: Valid (after DC braking)
0
Communication error trip time
Communication waiting time
Setting of master and slave for
communication between inverters
Adjustment range
Default setting
Communication command point 1 setting
Communication command point 1 frequency
-
(Hz)
0.0
0.0
Communication command point 2 setting
-
(Hz)
0.0
Communication command point 2 frequency
-
(Hz)
0.0
Selection of communication protocol
-
(Hz)
-
(Hz)
0.0
Block write data 1
(Hz)
0.0
Block write data 2
-
(Hz)
0.0
Block read data 1
-
(Hz)
0.0
Block read data 2
Block read data 3
Block read data 4
Block read data 5
Adjustment range
Default setting
Detailed protection settings parameters
0: Invalid, 1: Valid
0
1.0-1000 (Ω)
* 1
Title
Function
0.01-30.00 (kW)
* 1
Stall prevention release mode
Small current detection current hysteresis
Small current trip/alarm selection
Small current detection current
Adjustment range
Default setting
Small current detection time
25-500 (Hz)
50/60
Detection of output short-circuit during start-up
50-330 (V)/50-660 (V)
230/460/575
Over-torque trip/alarm selection
0-30 (%)
* 1
Over-torque detection level
10-100 (%/A)
100
Over-torque detection time
10-199 (%/A), 200: Invalid
150
Over-torque detection level hysteresis
Cumulative operation time alarm setting
Over-voltage stall protection level
Undervoltage trip/alarm selection
Adjustment range
Adjustment range
Default setting
Trip at VIA low level input mode
0.0-3200 (s)
10.0
Annual average ambient temperature
0.0-3200 (s)
10.0
(parts replacement alarms)
0: Linear, 1: S-pattern 1, 2: S-pattern 2
0
0: Linear, 1: S-pattern 1, 2: S-pattern 2
0
1: Acc/dec 1, 2: Acc/dec 2, 3: Acc/dec 3
1
0.0-
(Hz)
0.0
Title
Function
0-50 (%)
10
Prohibition of parameter change
0-50 (%)
10
Prohibition of frequency setting on the operation panel (
0.0-3200 (s)
10.0
Panel operation prohibition (RUN/STOP keys)
0.0-3200 (s)
10.0
Prohibition of panel emergency stop operation
0: Linear, 1: S-pattern 1, 2: S-pattern 2
0
Prohibition of panel reset operation
0.0-
(Hz)
0.0
Prohibition of
/
/
during operation
External connection input up/down setting parameters
Adjustment range
Default setting
- 20.0 (Hz)
5.0
Title
Function
0, 1, 2
0
Input from external contacts- UP response time
0: Invalid, 1: Valid
0
Input from external contacts- UP frequency step width
Input from external contacts- DOWN response time
Input from external contacts- DOWN frequency step width
Initial value of UP/DOWN frequency
Adjustment range
Default setting
Saving of changed value of UP/DOWN frequency
0-
0-
(Hz)
(Hz)
0.0
0-30 (Hz)
0-30 (Hz)
0.0
Torque up detailed setting parameter
0-
0-
(Hz)
(Hz)
0.0
0-30 (Hz)
0-30 (Hz)
0.0
Title
Function
0-
0-
(Hz)
(Hz)
0.0
Exciting current coefficient
0-30 (Hz)
0-30 (Hz)
0.0
Stall prevention control coefficient 1
Stall prevention control coefficient 2
Motor adjustment coefficient
Maximum voltage adjustment coefficient
Adjustment range
Default setting
Waveform switching adjustment coefficient
0: Reverse, 1: Slowdown Stop
1
Starting current suppression function
0.5-10 (Hz)
0.5
0-
(Hz)
0.0
Others/option settings parameters
0-
(Hz)
0.0
0: Invalid, 0.1-600 (s)
0.1
Title
Function
0, 1, 2
0
Droop gain
Droop insensitive torque band
Braking mode selection
Release frequency
Adjustment range
Default setting
Release time
0: Logic output, 1: Pulse train output
0
Creeping frequency
0-17 (Same as
)
0
Creeping time
500-1600(PPS)
800
Free notes
1
0: Negative inclination, 1: Positive inclination
Parameter for option 1
0-100 (%)
0
Parameter for option 2
Parameter for option 3
Parameter for option 4
Parameter for option 5
Adjustment range
Default setting
Step-out detection current level
0-2400 (s)
0
Step-out detection time
0: Invalid, 1: Valid
0
High-speed torque adjustment coefficient
0.01-100.0
0.30
* 1: Default values vary depending on the capacity.
0.01-100.0
0.20
0.00-2.55
0
Adjustment range
Default setting
0, 1, 2, 3, 4
3
0, 1, 2
1
0-255
0
0: Invalid, 1-100 (s)
0
0-2 (s)
0.00
0, 1, 2, 3, 4
0
0-100 (%)
0
0.0-500.0 (Hz)
0.0
0-100 (%)
100
0.0-500.0 (Hz)
60.0
0, 1
0
0-5
0
0-5
0
0-10
0
0-10
0
0-10
0
0-10
0
0-10
0
Adjustment range
Default setting
0, 1
0
1-20
10
0: Alarm only, 1: Tripping
0
0-100 (%)
0
0-255 (s)
0
0, 1, 2, 3
0
0: Alarm only, 1: Tripping
0
0-250 (%)
150
0-10 (s)
0.5
0-100 (%)
10
0-999.9
610
100-150 (%)
*1
0, 1, 2
0
0:
, 1-100 (%)
0
Invalid
1, 2, 3, 4, 5, 6
3
Panel settings parameters
Adjustment range
Default setting
0: Permitted, 1: Prohibited
0
)
0: Permitted, 1: Prohibited
0
0: Permitted, 1: Prohibited
0
0: Permitted, 1: Prohibited
0
0: Permitted, 1: Prohibited
0
change
0: Permitted, 1: Prohibited
1
Adjustment range
Default setting
0.0-10.0 (s)
0.1
0.0-
(Hz)
0.1
0.0-10.0 (s)
0.1
0.0-
(Hz)
0.1
(Hz)
0.0
0, 1
1
Adjustment range
Default setting
100-130 (%)
100
10-250
100
50-150
100
0-200
* 1
90-120 (%)
104
0.1-14.0 (kHz)
0.2
0: Invalid, 1: Valid
0
Adjustment range
Default setting
0-100 (%)
0
0-100 (%)
10
0, 1, 2, 3
0
-20.0 (Hz)
3.0
0.00-2.50 (s)
0.05
-20.0 (Hz)
3.0
0.00-2.50 (s)
0.10
0-65535
0
0-65535
0
0-65535
0
0-65535
0
0-65535
0
0-65535
0
10-150 (%/A)
100
0.0: Invalid, 0.1-25.0 (s)
0.0
0.00-650.0
0.00