Download Print this page

Toshiba TOSVERT VF-S11 Specifications page 10

Transistor inverter
Hide thumbs Also See for TOSVERT VF-S11:

Advertisement

Devices
External dimensions and connections
Input AC reactor
(ACL)
Fig. A
Model
Rating
Inverter type
1-phase 240V -2.0A-50/60Hz
VFS11S-2002PL
PFLS2002S
VFS11-2004
PFL2005S
3-phase 240V -5.5A-50/60Hz
VFS11S-2004PL
VFS11-2015
PFL2011S
3-phase 240V -11A-50/60Hz
VFS11S-2007PL
VFS11-2037PM
PFL2018S
3-phase 240V -18A-50/60Hz
VFS11S-2015
PFL2025S
3-phase 240V -25A-50/60Hz
VFS11-2055PM
PFL2050S
3-phase 240V -50A-50/60Hz
VFS11-2075 2110PM
PFL2100S
3-phase 240V -100A-50/60Hz
VFS11-2150PM
PFL4012S
3-phase 500V -12.5A-50/60Hz
VFS11-4004 4037PL
PFL4025S
3-phase 500V -25A-50/60Hz
VFS11-4055 4110PL
PFL4050S
3-phase 500V -50A-50/60Hz
VFS11-4150PL
Note: PFLS2002S has 4 terminals.
DC reactor
(DCL)
4.5 x 6 slotted hole (DCLS-2002)
4.4 x 6 slotted hole (DCL-2007)
Fig. A
Terminal box
with cover
Name
Plate
Fig. C
Rated
current
Inverter type
Model
(A)
DCLS-2002
2.5
VFS11S-2002PL
VFS11-2004
2007PM
DCL-2007
7
VFS11S-2004PL
VFS11-2015
2022PM
DCL-2022
14
VFS11S-2007PL
VFS11-2037PM
DCL-2037
22.5
VFS11S-2015
2022PL
DCL-2055
38
VFS11-2055PM
DCL-2110
75
VFS11-2075 2110PM
DCL-2220
150
VFS11-2150PM
DCL-2007
7
VFS11-4004 4015PL
DCL-2022
14
VFS11-4022 4037PL
DCL-4110
38
VFS11-4055 4110PL
DCL-4220
75
VFS11-4150PL
Note: VFS11-4004PL-4037PL are used DC reactor for 240V class.
VFS11
AC reactor
Terminal box with cover
Power
source
VFS11S
AC reactor
Power
source
4-ØF holes
Fig. B
Dimensions (mm)
Approx.
Terminals
weight
A
B
C
D
E
F
G
(kg)
Harmonica
80
55
115
63
45
5
45
0.85
(Note)
terminal M3.5
2007PM
Harmonica
105
65
115
90
55
5
40
1.2
terminal M3.5
2022PM
Harmonica
130
70
140
115
60
5
50
2.3
terminal M4
A
Harmonica
130
70
140
115
60
5
50
2.5
2022PL
terminal M4
Harmonica
125
100
130
50
83
7
2.6
terminal M4
Harmonica
155
115
140
50
95
7
3.4
terminal M6
B
Harmonica
230
150
210
60
90
8
8.2
terminal M8
125
95
130
50
79
7
2.3
Harmonica
terminal M4
155
7
4.9
110
155
50
94
B
Harmonica
155
140
165
50
112
7
6.6
terminal M6
Terminal box
with cover
Name plate
Name plate
Fig. B
DC reactor
PA/+
Power
source
Approx.
Dimensions (mm)
Terminals
weight
W
H
D
X
Y
d1
d2
(kg)
79
50
44
66
V1.25-3.5
A
92
65
70
82
V2-3.5
86
110
80
71
64
M4
B
86
110
85
71
70
M4
75
130
140
50
85
85
55
M5
100
150
150
65
85
95
55
C
M6
117
160
190
90
90
130
60
M8
92
65
70
82
A
V2-3.5
(Note)
86
110
80
71
64
B
M4
(Note)
95
150
165
70
90
105
60
M5
C
105
160
185
80
100
130
65
M8
Devices
High-attenuation
radio noise filter
(NF type)
Zero-phase reactor
ferrite core-type
radio noise filter
Braking
resistor
0.6
1.2
2.2
2.5
1.9
2.4
4.3
1.2
2.2
3.0
3.7
External dimensions and connections
P (Earth terminal)
Rated
Dimensions (mm)
Reactor
current
Inverter type
model
A
B
C
E
F
(A)
NF3005A-MJ
5
VFS11-2004PM VFS11-2007PM
VFS11-2015PM, VFS11-2022PM
NF3015A-MJ
15
174.5
160
145
110
80
NF3020A-MJ
20
VFS11-2037PM
VFS11-2055PM
NF3030A-MJ
30
NF3040A-MJ
40
VFS11-2075PM
217.5
200
185
120
90
VFS11-2110PM
NF3050A-MJ
50
267.5
250
235
170
140
NF3080A-MJ
80
VFS11-2150PM
294.5
280
260
170
150
VFS11-4004 4037PL
NF3010C-MJ
10
NF3015C-MJ
15
VFS11-4055PL
174.5
160
145
110
80
VFS11-4075PL
NF3020C-MJ
20
NF3030C-MJ
30
VFS11-4110PL
177.5
200
185
120
90
VFS11-4150PL
NF3040C-MJ
40
217.5
Note: Every inverter with a model number ending in-PL comes standard with a built-in noise filter almost equal in size and performance to this filter.
7 x 14 slotted hole
Unit: mm
Model: RC5078
Model: RC9129
B
E (Installation dimension)
4.2
Power source
500
(Lead wire length)
C
Fig. A
4-ø5 holes
Wire opening
(Note 1)
Earth terminal
(M5)
D (Installation dimension)
Fig. B
Rating
Inverter type
Model
VFS11-2004
2007PM
PBR-2007
120W-200
VFS11S-2002
2007PL
VFS11-2015, 2022PM
PBR-2022
120W-75
VFS11S-2015, 2022PL
PBR-2037
120W-40
VFS11-2037PM
PBR3-2055
240W-20 (40
2P)
VFS11-2055PM
PBR3-2075
440W-15 (30
2P)
VFS11-2075PM
PBR3-2110
660W-10 (30
3P)
VFS11-2110PM
PBR3-2150
880W-7.5 (30
4P)
VFS11-2150PM
PBR-2007
120W-200
VFS11-4004 4022PL
PBR-4037
120W-160
VFS11-4037PL
PBR3-4055
240W-80 (160
2P)
VFS11-4055PL
PBR3-4075
440W-60 (120
2P)
VFS11-4075PL
PBR3-4110
660W-40 (120
3P)
VFS11-4110PL
PBR3-4150
880W-30 (120
4P)
VFS11-4150PL
Note1: Use the same type of braking resistor of VFS11-2002 ~ 2007PM for those of VFS11-4004 ~ 4022PL.
Note2: The data in Rating above refer to the resultant resistance capacities (watts) and resultant re-sistance values (_).
The numeric values inside parentheses refer to the internal compositions of resistors.
LC filter
Power
source
Note:(1) Noise filter should be connected to
the inverter main circuit primaryside.
(2) Output cable should be kept away
from the input cable.
Approx.
weight
G
H
J
K
M
N
P
(kg)
1.0
32
45
M4
70
20
Ø5.5
M4
1.6
43
M5
2.7
44
90
60
4.6
30
Ø6.5
M6
37
100
65
M6
7.0
1.4
32
45
M4
70
20
1.6
Ø5.5
M4
44
43
M5
2.7
Zero-phase reactor
VF-S11
R
U
Power
S
V
IM
source
T
W
Motor
Input or output cable sould be coiled over 4-times.
RC5078 is recommended for the models
4.0kW or less.
VF-S11
R
U
S
V
IM
T
W
PB
PA
Fig. C
Breaking resistor
VF-S11
R
U
Power
S
V
IM
source
T
W
MC
PB
PA/+
ON
E
PB
PA
OFF
E
Breaking resistor
MC
TH1
TH2
FLB
FLC
Do not fail connect to
TH1
the operation circuit
TH2
Fig. D
External
Approx.
Dimensions (mm)
dimensions
weight
and
A
B
C
D
E
G
(kg)
connections
A
42
182
20
4.2
172
and
0.28
C
320
115
50
4
B
4.5
120
110
230
and
350
190
150
5
D
5.5
A
42
182
20
4.2
172
and
0.28
C
320
115
50
4
B
4.5
120
110
230
and
350
190
150
5
D
5.5

Advertisement