Mitsubishi Electric PUHZ-SW40VHA Service Manual page 45

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-SW40VHA:
Table of Contents

Advertisement

Indication
Outdoor controller board
LED1 (Green) LED2 (Red)
3 blinking 1 blinking
Abnormality of comp.surface thermistor(TH34)
and discharging temperature (TH4)
Abnormality of superheat due
to low discharge temperature
2 blinking
Abnormal high pressure (High
pressure switch 63H operated.)
3 blinking
Abnormality of outdoor fan
motor rotational speed
Protection from overheat operation(TH3)
Compressor overcurrent
4 blinking
breaking(Start-up locked)
Compressor overcurrent breaking
Abnormality of current sensor (P.B.)
Abnormality of power module
Open/short of discharge thermistor (TH4)
5 blinking
and comp.surface thermistor (TH34)
Open/short of outdoor thermistors
(TH3, TH6, TH7 and TH8)
Abnormality of heatsink
6 blinking
temperature
7 blinking
Abnormality of voltage
4 blinking
1 blinking
Abnormality of room temperature thermistor (TH1)
Abnormality of pipe temperature thermistor /Liquid (TH2)
Abnormality of pipe temperature
thermistor/Condenser-Evaporator
2 blinking
Abnormality of drain sensor (DS)
Float switch(FS) connector open
Indoor drain overflow protection
3 blinking
Freezing (cooling)/overheating
(heating) protection
Abnormality of pipe
4 blinking
temperature
*1 Error code displayed on remote controller
*2 Refer to service manual for indoor unit.
OCH525
Error
Contents
code
1
U2
U7
U1
U8
Ud
UF
UP
UH
U6
U3
U4
U5
U9
P1
P2
P9
P4
P5
P6
P8
Error
Inspection method
Check if stop valves are open.
Check if connectors (TH4, TH34, LEV-A, and LEV-B) on outdoor controller
board are not disconnected.
Check if unit is filled with specified amount of refrigerant.
Measure resistance values among terminals on indoor valve and
outdoor linear expansion valve using a tester.
Check if indoor/outdoor units have a short cycle on their air ducts.
Check if connector (63H) on outdoor controller board is not disconnected.
Check if heat exchanger and filter is not dirty.
Measure resistance values among terminals on linear expansion valve
using a tester.
Check the outdoor fan motor.
Check if connector (TH3) on outdoor controller board is disconnected.
Check if stop valves are open.
Check looseness, disconnection, and converse connection of
compressor wiring.
Measure resistance values among terminals on compressor using a tester.
Check if outdoor unit has a short cycle on its air duct.
Check if connectors(TH3,TH4,TH6 ,TH7 and TH34)on outdoor controller
board and connector (CN3) on outdoor power board are not disconnected.
Measure resistance value of outdoor thermistors.
Check if indoor/outdoor units have a short cycle on their air ducts.
Measure resistance value of outdoor thermistor(TH8).
Check looseness, disconnection, and converse connection of
compressor wiring.
Measure resistance value among terminals on compressor using a tester.
Check the continuity of contactor (52C).
Check if power supply voltage decreases.
Check the wiring of CN52C.
Check the wiring of CNAF.
Check if connectors (CN20, CN21, CN29 and CN44) on indoor
controller board are not disconnected.
Measure resistance value of indoor thermistors.
Check if connector (CN31)(CN4F) on indoor controller board is not
disconnected.
Measure resistance value of indoor thermistors.
Measure resistance value among terminals on drain pump using
a tester.
Check if drain pump works.
Check drain function.
Check if indoor unit has a short cycle on its air duct.
Check if heat exchanger and filter is not dirty.
Measure resistance value on indoor and outdoor fan motors.
Check if the inside of refrigerant piping is not clogged.
Check if indoor thermistors(TH2 and TH5) are not disconnected from holder.
Check if stop valve is open.
Check converse connection of extension pipe. (on plural units connection)
Check if indoor/outdoor connecting wire is connected correctly.
(on plural units connection)
45