Mitsubishi Electric Mr.Slim PUHZ-SHW80VHA Service Manual page 70

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PUHZ-SHW80VHA:
Table of Contents

Advertisement

SW2 setting
LEV-A opening pulse on error occurring
0~480
ON
1
2 3 4 5 6
Indoor room temperature (TH1) on error
occurring
ON
8~39
1
2 3 4 5 6
Indoor pipe temperature / Liquid (TH2)
on error occurring
ON
-39~88
1
2 3 4 5 6
Pressure saturation temperature (T
on error occurring
ON
-39~88
1
2 3 4 5 6
Outdoor pipe temperature / Cond./ Eva.
(TH6) on error occurring
-39~88
ON
1
2 3 4 5 6
Outdoor outside temperature (TH7) on
error occurring
ON
-39~88
1
2 3 4 5 6
Outdoor heatsink temperature (TH8) on
error occurring
-40~200
ON
1
2 3 4 5 6
OCH526
Display detail
63HS
The black square (
Explanation for display
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 secs.
8~39
-39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
)
-39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
-39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
-39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
-40~200
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
70
) indicates a switch position.
0.5secs.
2 secs.
1
30
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
Unit
Pulse
:
:
:
:
:
:

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents