How To Proceed "Self-Diagnosis - Mitsubishi Electric Mr.Slim PUHZ-SHW80VHA Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PUHZ-SHW80VHA:
Table of Contents

Advertisement

9-3. HOW TO PROCEED "SELF-DIAGNOSIS"

9-3-1. When a Problem Occurs During Operation
If a problem occurs in the air conditioner, the indoor and outdoor units will stop,
and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the
temperature display, and the error code and unit number are
displayed alternately as shown below. (If the outdoor unit is
malfunctioning, the unit number will be "00".)
In the case of group control, for which one remote controller controls
multiple refrigerant systems, the refrigerant address and error code of
the unit that first experienced trouble (i.e., the unit that transmitted
the error code) will be displayed.
To clear the error code, press the
When using remote-/local-controller combined operation, cancel the error code after turning off remote operation. During
central control by a MELANS controller, cancel the error code by pressing the
9-3-2. Self-Diagnosis During Maintenance or Service
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the remote
controller or power is turned off.
Check the error code history for each unit using the remote controller.
Switch to self-diagnosis mode.
Press the
button twice within 3 seconds. The display content
CHECK
will change as shown below.
Unit number or refrigerant address
to be diagnosed
Display self-diagnosis results.
<When there is error code history>
(For the definition of each error code, refer to the indoor unit's installation manual or service handbook.)
<When there is no error code history>
Reset the error history.
Display the error history in the diagnosis result display screen (see step
OCH526
ON/OFF
button.
(Alternating Display)
Error code (2 or 4 digits)
(Alternating Display)
Error code (2 or 4 digits)
Address (3 digits) or unit number (2 digits)
Set the unit number or refrigerant address you want to diagnose.
Press the [TEMP] buttons (
or address. The number (address) changes between [01] and [50] or [00]
and [15].
The refrigerant address will begin to blink
approximately 3 seconds after being
selected and the self-diagnosis process will begin.
Address (3 digits) or unit number (2 digits)
<When there is no corresponding unit>
).
20
button.
ON/OFF
and
) to select the desired number

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents