Mitsubishi Electric Mr.Slim PUHZ-SHW80VHA Service Manual page 66

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PUHZ-SHW80VHA:
Table of Contents

Advertisement

SW2 setting
Pipe temperature / Liquid (TH3) on error
occurring
ON
– 40~90
1
2 3 4 5 6
Discharge temperature (TH4) on error
occurring
ON
3~217
1
2 3 4 5 6
Compressor operating current on error
occurring
ON
0~20
1
2 3 4 5 6
Error code history (1) (latest)
Alternate display of abnormal unit
ON
number and code
1
2 3 4 5 6
Error code history (2)
Alternate display of error unit number
ON
and code
1
2 3 4 5 6
Thermo ON time
0~999
ON
Test run elapsed time
1
2 3 4 5 6
0~120
OCH526
Display detail
The black square (
Explanation for display
– 40~90
(When the coil thermistor detects 0: or below, "–"
and temperature are displayed by turns.)
(Example) When –15:;
0.5 secs.
3~217
(When the temperature is 100: or more, the
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 130:;
0.5 secs.
0~20
When no error history,
" 0 " and "– –" are displayed by turns.
When no error history,
" 0 " and "– –" are displayed by turns.
0~999
(When it is 100 minutes or more, the hundreds digit,
tens digit and ones digit are displayed by turns.)
(Example) When 245 minutes;
0.5 secs.
0~120
(When it is 100 minutes or more, the hundreds digit,
tens digit and ones digit are displayed by turns.)
(Example) When 105 minutes;
0.5 secs.
66
) indicates a switch position.
0.5secs.
2 secs.
15
0.5secs.
2 secs.
1
30
0.5secs.
2 secs.
2
45
0.5secs.
2 secs.
1
05
Unit
:
:
A
Code
display
Code
display
Minute
Minute

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents