FUNCTIONAL
SPECIFICATIONS
PHYSICAL
SPECIFICATIONS
Smart Wireless THUM Adapter
Reference Data
Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . page A-1
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . page A-2
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-3
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-5
Input
Any 2- or 4-wire HART powered device.
Output
IEC 62591 (WirelessHART)
Humidity Limits
0–100% relative humidity
Update Rate
User selectable, 8 sec. to 60 min.
Electrical Connections
The THUM is connected into a powered 4–20 mA loop, powering itself by
scavenging power. The THUM causes a voltage drop across the loop. The
drop is linear from 2.25 volts at 3.5 mA to 1.2 volts at 25 mA, but does not
effect the 4–20 mA signal on the loop. Under fault conditions, the maximum
voltage drop is 2.5 volts.
Power Supply
Minimum load on loop 250 Ohms.
To maintain normal operating functions of the sub-device, the power in the
loop must have at least a 2.5 V margin at a 250 Ohm load.
Limit power supply to 0.5 Amps maximum.
Limit power supply to 55 Vdc maximum.
Field Communicator Connections
Utilize sub-device HART connections.
Materials of Construction
Housing option D - Low-copper aluminum
Housing option E - 316 SST
Paint - Polyurethane
M20-Conduit Adapter - SST
M20-Conduit Adapter O-ring - Buna-n
Antenna
Poly butadine terephthalate (PBT) / Polycarbonate (PC) integrated
omnidirectional antenna