Vent Components Diagrams (con't)
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be
used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the
existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B
will be required.
15-1/8 in.
(384 mm)
8 in.
(203 mm)
12 in.
(305 mm)
Horizontal Termination Cap
DVP-TRAP1
DVP-TRAP2
DVP-HPC1
DVP-HPC2
Heatilator • GDST5244I • 4045-127 Rev Q • 02/07
Heat
Shield
Term Cap Effective Length Effective Length
TRAP1
TRAP2
Max
Effective
Length
DVP-TRAP
DVP-TRAPK1
DVP-TRAPK2
DVP-HPCK1-B
DVP-HPCK2-B
Minimum
Maximum
4-1/8 in.
5-5/8 in.
105 mm
143 mm
6-3/4 in.
10-5/8 in.
171 mm
270 mm
51