CHIMNEY CONNECTOR
Your chimney connector (commonly called stove pipe) and chimney must have the same diameter as the 
stove's exhaust outlet. The stove pipe must be made of aluminized or cold roll steel with a minimum 24‐
gauge thickness (0.021" or 0.53 mm).  It is strictly forbidden to use galvanized steel. 
 
The following recommendations may be useful for the installation of your chimney connector: 
 
Your  chimney  connector  should  be  assembled  in  such  a  way  that  the  male  end  (crimped)  faces 
down to prevent creosote dripping outside the joints. Attach each of the sections to one another 
with  three  equidistant  metal  screws.    Also  use  three  equidistant  metal  screws  to  attach  the 
connector to the stove's exhaust collar.  See Figure 2.3 (A) and Figure 2.3 (B). 
The pipe must be short and straight.  All sections installed horizontally must slope at least ¼ inch 
per foot, with the upper end of the section toward the chimney. See Figure 2.3 Detail B. 
To insure a good draft, the total horizontal length of the connector should never exceed 8' to 10' 
(2.4 to 3.04 m).  In the case of vertical installation, the total length of the connector can be much 
longer and connected without problem to the chimney at the ceiling level. 
There  should  never  be  more  than  two  90  degrees  elbows  in  the  whole  connector  and  chimney 
system. Never start with a 90
before using a 90
The  connector  must  not  pass  through  any  combustible  material,  nor  may  it  pass  through  a 
concealed space (such as an attic, roof space, or closet). If passing through a wall, ceiling, or into a 
masonry chimney, use either chimney components listed for that specific use, or means acceptable 
to local authorities having jurisdiction over the installation. 
Installation  of  a  "barometric  draft  stabiliser"  (fireplace  register)  on  a  connector  is  not 
recommended. 
o
 elbow.  Always go up vertically for at least 2 feet from the flue spigot 
o
 elbow. 
FIGURE 2.3 (A) Connecting Sections
 