Termination Clearances - White Mountain Hearth DVX36FP32CL(N,P)-1 Installation Instructions And Owner's Manual

Luxury direct vent gas fireplace heater
Table of Contents

Advertisement

Termination clearance for buildings with combustible and noncombustible exteriors.
INSIDE CORNER
"A" = COMBUSTIBLE 9" (229mm)
= NONCOMBUSTIBLE 2" (51mm)
BALCONY
WITH PERPENDICULAR SIDE WALL
"G" = COMBUSTIBLE 9" (229mm)
= NONCOMBUSTIBLE 2" (51mm)
"H" = COMBUSTIBLE 18" (457mm)
= NONCOMBUSTIBLE 12" (305mm)
Vertical Sidewall Installations
Important! Minimum clearance between vent pipes and combustible materials is three (3") (76mm) on top, and (1") (25mm) on bottom
and sides.
Important! When vent termination exits through foundation less than 20" below siding outcrop, the vent pipe must flush up with the
siding. SD-1284 or SD-985 termination cap must be used.
Information on Various Venting Routes and Components
Important: It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain
limitations as to vent configurations apply and must be strictly adhered to.
The graph showing the relationship between vertical and horizontal side wall venting will help to determine the various vent lengths
allowable.
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.
The maximum horizontal vent run is 20 feet (457 cm) when the vertical vent rise is 8 feet (244 cm). See Figure 17.
Venting terminals shall not be recessed into wall or siding.
23835-1-0607

TERMINATION CLEARANCES

OUTSIDE CORNER
"F" = COMBUSTIBLE 6" (152mm)
= NONCOMBUSTIBLE 6" (152mm)
BALCONY
WITH NO SIDE WALL
"I" = COMBUSTIBLE 18" (457mm)
= NONCOMBUSTIBLE 12" (305mm)
"C" = CLEARANCE FROM CORNER
"D" = MINIMUM WIDTH FOR BACK WALL
"E" = MAXIMUM DEPTH OF 48" (1219mm)
Figure 44
RECESSED LOCATION
IN RECESSED LOCATION
COMBUSTIBLE 9" (229mm)
NONCOMBUSTIBLE 2" (51mm)
OF A RECESSED LOCATION
COMBUSTIBLE 38" (965mm)
NONCOMBUSTIBLE 24" (610mm)
FOR RECESSED LOCATION