21. TROUBLESHOOTING GUIDE
WARNING
SEQUENCE OF EVENTS
APPLY 120 VOLTS
SET THERMOSTAT TO CALL FOR HEAT
COMBUSTION AIR BLOWER STARTS
YES
Air Proving Switch HAS CLOSED
(Blocked Flue Switch REMAINS CLOSED)
24 VOLTS PRESENT AT DSI CONTROL.
YES
SPARK IGNITER / SENSOR
YES
24V TO GAS VALVE
CONTINUED
Improper adjustment, alteration, service or maintenance can
cause property damage, injury or death. This heater must be
installed and serviced only by a trained gas service technician
CHECK IF 120 VOLTS PRESENT AT BLOWER
NO
IF "YES".....REPLACE DEFECTIVE BLOWER
NO
CHECK 24V SUPPLY TO RELAY SWITCH
CHECK 120V SUPPLY TO RELAY SWITCH
IF ELECTRICAL SUPPLY PROBLEM .... MAKE RE-
QUIRED REPAIR TO RESTORE 120V
CHECK FOR 120V FROM RELAY SWITCH
IF "NO" SWITCHING IS OCURRING......REPLACE
THE RELAY SWITCH
CHECK FOR OBSTRUCTION IN THE AIR INTAKE
NO
AND FLUE
CHECK TUBING TO SWITCHES IS CONNECTED
AND NOT BLOCKED OR KINKED
CHECK IF AIR PROVING SWITCH IS CLOSING
WHEN BLOWER IS RUNNING
CHECK AIR PRESSURE WITH MANOMETER
REPLACE ANY DEFECTIVE SWITCH
CHECK DSI CONTROL FUSE FOR CONTINUITY
NO
VISIBLY CHECK IF IGNITER IS SHORTING OUT
CHECK GROUND WIRING
REMOVE AND INSPECT IGNITER AND LEAD
CHECK BOOT OF THE IGNITION CABLE FOR SIGNS
OF MELTING OR OVERHEATING
IF "YES" ... TAKE PROTECTIVE ACTION TO SHIELD
CABLE AND BOOT FROM EXCESSIVE TEMPERA-
TURE; REPLACE ANY DEFECTIVE COMPONENT
CHECK CERAMIC INSULATOR AND CAP
CHECK SPARK GAP SETTING IS 3/16" (ADJUST BY
MOVING THE GROUND PRONG ONLY)
PERFORM IGNITION LEAD TEST (See SPARK IGNI-
TION CIRCUIT INSTRUCTIONS—Section 22)
GOOD SPARK.....REPLACE IGNITER
NO SPARK/OR WEAK.....REPLACE CONTROL
37
S100/ITB I&O Manual
IM101230
RD: JAN 2012
RL: 6B- BA