Gas Piping; Side Return Cutout Markings; Gas Valve - Johnson Controls TM9X*MP Installation Manual

High efficiency motor residential gas furnace
Table of Contents

Advertisement

697936-UIM-B-01211
SIDE RETURN
Locate the "L" shaped corner locators. These indicate the size of the cut-
out to be made in the furnace side panel. Refer to Figure 14.
FIGURE 14: Side Return Cutout Markings
Install the side filter rack following the instructions provided with that
accessory. If a filter(s) is provided at another location in the return air
system, the ductwork may be directly attached to the furnace side
panel.
Some accessories such as electronic air cleaners and pleated media
may require a larger side opening. Follow the instructions supplied
with that accessory for side opening requirements. Do not cut the
opening larger than the dimensions shown in Figure 13.
HORIZONTAL APPLICATION
Horizontal Filters
All filters and mounting provision must be field supplied. All installa-
tions must have a filter installed.
Any branch duct (rectangular or round duct) attached to the plenum
must attach to the vertical plenum before the filter. The use of straps
and/or supports is required to support the weight of the external filter
box.
Downflow Filters
Downflow furnaces typically are installed with the filters located above
the furnace, extending into the return air plenum or duct. Any branch
duct (rectangular or round duct) attached to the plenum must attach to
the vertical plenum above the filter height.
Filter(s) may be located in the duct system external to the furnace using
an external duct filter box attached to the furnace plenum or at the end
of the duct in a return filter grille(s). The use of straps and/or supports is
required to support the weight of the external filter box.
To Gas
Supply
External
Manual
Shut-off
Valve
Ground
Union
Drip
Leg
Upflow
FIGURE 16: Gas Piping
10
Front of
Furnace
Side of
Furnace
Corner
Markings
To Gas
NOTE: Ground Union maybe installed inside or outside unit.
Supply
Ground
Union
To Gas
Supply
Gas
Valve
Gas
Pipe
Drip
Leg
Ground
Union
Gas
Drip
Pipe
Leg
Downflow
SECTION IV: GAS PIPING
GAS SAFETY
An overpressure protection device, such as a pressure regulator,
must be installed in the gas piping system upstream of the furnace
and must act to limit the downstream pressure to the gas valve so it
does not exceed 0.5 psig [14" w.c. (3.48 kPa)]. Pressures exceeding
0.5 psig [14" w.c. (3.48 kPa)] at the gas valve will cause damage to
the gas valve, resulting in a fire or explosion or cause damage to the
furnace or some of its components that will result in property damage
and loss of life.
Outlet
Pressure
Port
Inlet
Wrench
Boss
Inlet
Pressure
Port
FIGURE 15: Gas Valve
Plan your gas supply before determining the correct gas pipe entry.
Use 90° service elbow(s), or short nipples and conventional 90°
elbow(s) to enter through the cabinet access holes.
GAS PIPING INSTALLATION
Properly sized wrought iron, approved flexible or steel pipe must be
used when making gas connections to the unit. If local codes allow the
use of a flexible gas appliance connection, always use a new listed con-
nector. Do not use a connector that has previously serviced another gas
appliance.
Some utility companies or local codes require pipe sizes larger than the
minimum sizes listed in these instructions and in the codes. The furnace
rating plate and the instructions in this section specify the type of gas
approved for this furnace - only use those approved gases. The instal-
lation of a drip leg and ground union is required. Refer to Figure 16.
External
Manual
Shut-off
To Gas
Valve
Supply
Ground
Union
Gas
Valve
Drip
Leg
DANGER
Vent Port
Main Regulator
Adjustment
On/Off Switch
(Shown in ON position)
Ground
Union
External Manual
Shut-off Valve
Gas
Valve
Gas
Pipe
Ground
Union
Horizontal
Drip
Johnson Controls Unitary Products
Outlet
To Gas
Supply
Drip Leg
To Gas
Supply