SELECTION OF INSTALLATION PLACE
Removal of transporting rubbers
• Before installation of the indoor unit, remove the two
protective rubbers for transportation which are
inserted between the reinforcing bracket for the fan
motor and the casing.
(Hand over the protective rubbers for transportation
to the customers and ask to keep them because
they are used for transportation such as
reinstallation.)
Protective rubbers for transportation
(remove)
Reinforcing bracket
3

INSTALLATION OF INDOOR UNIT

Install the air conditioner certainly to sufficiently withstand the weight.
If the strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work to guard against strong wind or earthquake.
An incomplete installation can cause accidents by the units falling and dropping.
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be
sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, hold the hooking metals (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).
• Carry the package by two or more persons, and do not bundle it with PP band at positions other than
specified.
• The hanging bolt pitch on longitudinal direction is not divided at center with the ceiling opening size.
Therefore, check the relational position in the External view.
If relational position is incorrect, the check panel cannot be installed.
Pull upward to
remove.
Casing
WARNING
REQUIREMENT
5
In case of wireless type
The sensor of indoor unit with wireless remote
controller can receive a signal within approx. 8m.
Based upon it, determine a place where the remote
controller is operated and the installation place of the
indoor unit.
• To prevent a malfunction, select a place where is not
influenced by a florescent light or direct sunlight.
• Two or more (Up to 6 units) indoor units with
wireless remote controller can be installed in the
same room.