Bradford White IGI-180R-10 Service Manual page 35

Tankless gas water heater
Hide thumbs Also See for IGI-180R-10:
Table of Contents

Advertisement

VI - TROUBLESHOOTING
Troubleshooting Flow Chart
BEFORE CARRYING OUT CHECKS MARKED WITH
A # SIGN, DISCONNECT THE POWER SUPPLY.
Examination
Nature of Fault
Point
E. Anti-frost
1. check anti-frost
heater does not
heater.
work.
2. Check frost
sensing switch
(cont.)
Diagnostic Point
2. Measure voltage
11 ~ 13 VDC
between orange (+) and
grey (-) of the water flow
servo connector B
.
2
3. Measure voltage
4 ~ 6 VDC
between brown ~ grey
of water flow servo
connector B
(Don not
2
turn water on)
(See page 44)
4. Measure voltage
4 ~ 6 VDC
between yellow ~ grey
of the water flow servo
connector B
(Do not
2
turn water on)
(See page 44)
1. # Disconnect
348 ~ 375Ω
connector F
and F
4
5
measure resistance
across each of the
heating elements. (white
wires)
(See page 45)
2. # Read resistance of
100 ~ 110Ω
the heating element that
is mounted on the front
of the heat exchanger.
(white wires)
(See page 45)
3. Read resistance of
33 ~ 39Ω
heating elements on the
heat exchanger outlet
hot water line.
(See page 45)
# Disconnect connector
Is resistance <1Ω
F
and measure across
after applying ice to
2
this switch for five
the bi-metal sensing
minutes?
switch located on the
upper right hand of the
heat exchanger. check
this switch at
temperatures below 37
°F. You can place an ice
cube against the switch
to activate it.
(See page 45)
35
Values
Y/N
Yes
Go to 4-3
No
Replace PCB
Yes
Go to D-4-4
No
Replace water
flow servo
sensor.
Yes
Normal
No
Replace water
flow servo
sensor.
Yes
Go to E-1-2
No
Replace Anti-
frost sensing
switch.
Yes
Go to E-2
No
Replace Anti-
frost heater
that is
defective.
Yes
Go to E-2
No
Replace Anti-
frost heater
that is
defective.
Yes
Check wiring
No
Replace Anti-
frost sensing
switch.
Service
Action
Procedure
IGI – 2
IGI – 3
IGI – 3