Venting - Bradford White BNTH Installation And Operation Instructions Manual

Table of Contents

Advertisement

Brute Elite
combustion air intake (see
Route the intake to the boiler as directly as possible. Seal
all joints. Provide adequate hangers. The unit must not
support the weight of the combustion air intake pipe.
Maximum linear pipe length allowed is shown in
Subtract 5 allowable linear ft. (1.5m) for every elbow used.
The connection for the intake air pipe is at the top of
the unit (see
Figure 9a or Figure
In addition to air needed for combustion, air shall
also be supplied for ventilation, including air required for
comfort and proper working conditions for personnel.

3.2 Venting

Failure to use CPVC or stainless steel venting for the
first 20" (285-600) / 30" (80-210) of vent material or for
any part of the venting that is installed inside a closet
may lead to property damage, personal injury or death.
The proper length of this material is supplied with boiler.
Boilers in U.S. may use pipe included with boiler.
Failure to use the appropriate vent material, installation
techniques, glues/sealants could lead to vent failure
causing property damage, personal injury or death.
All venting must be installed according to this manual
and any other applicable local codes, including but not
limited to, ANSI Z223.1/NFPA 54, CSA B149.1,
CSAB149.2 and ULC-S636. Failure to follow this
manual and applicable codes may lead to property
damage, severe injury, or death.
The flue temperature of the Brute Elite changes
dramatically with changes in operating water
temperature. Therefore, it is necessary to assess the
application of the boiler to determine the required
certified vent class. If the Brute Elite is installed in
an application where the ambient temperature is
elevated, and/or installed in a closet/alcove, CPVC or
stainless steel material is required. If the system
temperatures are unknown at the time of
installation, class IIB or higher venting material is
recommended.
The Brute Elite is a Category IV appliance and
may be installed with PVC and CPVC that complies
with ANSI/ASTM D1785 F441, or a stainless steel
venting system that complies with UL 1738 Standard
(see
Table
5).
MATERIAL
Stainless Steel
PVC, sch 40
CPVC, sch 40
Table
4), sized per
Table
Table
9b).
WARNING
WARNING
WARNING
UNITED STATES
UL 1738
ANSI/ASTM D178
ANSI/ASTM F441
Table 5. Required Exhaust Vent Material.
2.
The unit's vent can terminate through the roof, or
through an outside wall.
When using PVC/CPVC for vent material, venting
must be connected to the CPVC section included with
2.
Brute Elite sizes 80-600. The CPVC vent section
included with the Brute Elite may be broken by CPVC
fittings if necessary, but never reduced in total length.
See
Table 2
to select the appropriate vent pipe diameter.
Vent pipe must pitch upward, toward the vent terminal,
not less than 1/4" per foot, so that condensate will run
back to the Brute Elite to drain. Route vent pipe to the
heater as directly as possible. Seal all joints and provide
adequate hangers as required in the venting system
manufacturer's Installation Instructions. Horizontal
portions of the venting system must be supported to
prevent sagging and may not have any low sections that
could trap condensate. The unit must not support the
weight of the vent pipe. Please see
diameter vs. length allowed.
IMPORTANT NOTE ABOUT COMMON VENTING: A
single vent that is shared by multiple Brute Elite units
MUST be engineered by a competent venting
specialist, and involves the selection of draft inducing
equipment, hardware and controls to properly balance
flue gas pressures. Do not common vent Brute Elite
Figure 10. Combustion Air and Vent Through Roof.
INSTALLATION STANDARDS
Venting must be ULC-S636 certified for use as
venting material. The venting material must be chosen
based upon the intended application of the boiler.
Page 13