Electrical Requirements; Ce Requirements - Bunn LCA-2 PC Installation & Operating Manual

Liquid coffee ambient/chilled dispenser
Hide thumbs Also See for LCA-2 PC:
Table of Contents

Advertisement

CAUTION: The dispenser must remain disconnected from the power source until specified in Electrical Hook-
Up.
The LCA-2 and LCC-2 dispensers are supplied with a 120-volt / 15 Amp cord set and require a 2-wire, grounded,
individual branch circuit rated for 120 volts AC, 15 amp, single phase, 60Hz. The mating connector must be
a NEMA 5-15R.
The LCA-2C and LCC-2C dispensers are supplied with a 120-volt / 20 Amp cord set and require a 2-wire,
grounded, individual branch circuit rated for 120 volts AC, 20 amp, single phase, 60Hz. The mating connector
must be a NEMA 5-20R.
These dispensers can be Field Wired for 208 or 240 volt applications. This requires a 2 or 3-wire, grounded,
individual branch circuit rated for 208/240 volts AC, 30 amp, single phase, 60 Hz.
NOTE: The internal terminal block must be rewired for 208/240 applications, (see Optional Field Wiring
Diagram).
HEATER RED
10A. FUSE - WHITE
10A. FUSE - BLACK
LIMIT SW. - BLACK
1. Unit shipped per Fig. 1, wired for 120V A.C./2-Wire.
2. For 208 - 240V A.C./2-Wire per Fig. 2: Move both the Red-Heater wire and the White-Fuse wire to the Top Red Terminal as shown.
3. For 120/208 - 240V A.C./3-Wire per Fig. 3: Move the Red Heater wire to the Top Red Terminal as shown.
RED
TO MASTER
ON/OFF
SWITCH
BLACK
1. Unit shipped per Fig. 1, wired for 120V A.C./2-Wire.
2. For 208 - 240V A.C./2-Wire per Fig. 2.
3. For 120/208 - 240V A.C./3-Wire per Fig. 3.
• This appliance must be installed in locations where it can be overseen by trained personnel.
• For proper operation, this appliance must be installed where the temperature is between 5°C to 35°C.
• Appliance shall not be tilted more than 10° for safe operation.
• An electrician must provide electrical service as specified in conformance with all local and national codes.
• This appliance must not be cleaned by water jet.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given instructions concerning use of
this appliance by a person responsible for its safety.
• Children should be supervised to ensure they do not play with the appliance.
• If the power cord is ever damaged, it must be replaced by the manufacturer or authorized service personnel with
a special cord available from the manufacturer or its authorized service personnel in order to avoid a hazard.

ELECTRICAL REQUIREMENTS

FIELD WIRING TERMINAL BLOCK DIAGRAM
Models without Master ON/OFF Switch
FIELD WIRING TERMINAL BLOCK DIAGRAM
HEATER RED
10A. FUSE - WHITE
120V A.C.
10A. FUSE - BLACK
Fig. 1
LIMIT SW. - BLACK
For all 208 - 240 Volt Connections: Use No. 10 AWG Wires suitable for 90°C (194 °F)
FIELD WIRING TERMINAL BLOCK DIAGRAM
Models with Master ON/OFF Switch
FIELD WIRING TERMINAL BLOCK DIAGRAM
TO MASTER
120V A.C.
ON/OFF
SWITCH
Fig. 1
For all 208 - 240 Volt Connections: Use No. 10 AWG Wires suitable for 90°C (194°F)

CE REQUIREMENTS

208 or
240V A.C.
Fig. 2
RED
208 or
240V A.C.
BLACK
Fig. 2
5
HEATER RED
120V A.C.
10A. FUSE - WHITE
208 or
240V A.C.
120V A.C.
10A. FUSE - BLACK
Fig. 3
LIMIT SW. - BLACK
RED
120V A.C.
TO MASTER
208 or
ON/OFF
240V A.C.
120V A.C.
SWITCH
BLACK
Fig. 3
34766 110408