Caution; Gas Piping - Lennox MERIT ML180UH Installation Instructions Manual

Merit series gas furnace upflow / horizontal air discharge
Hide thumbs Also See for MERIT ML180UH:
Table of Contents

Advertisement

Gas Piping

Gas supply piping should not allow more than 0.5"W.C. drop
in pressure between gas meter and unit. Supply gas pipe
must not be smaller than unit gas connection.

CAUTION

If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet. The flexible connector can then
be added between the black iron pipe and the gas
supply line.
Gas Supply
1 − This unit is shipped standard for left or right side instal-
lation of gas piping (or top entry in horizontal applica-
tions). Connect the gas supply to the piping assembly.
2 − When connecting the gas supply piping, consider fac-
tors such as length of run, number of fittings, and fur-
nace rating to avoid excessive pressure drop. Table 9
lists recommended pipe sizes for typical applications.
3 − The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waiters,
or elevator shafts.
Nominal
Internal
Iron Pipe
Diameter
Size
inches
inches
(mm)
(3.048)
(mm)
1/2
.622
172
(12.7)
(17.799)
(4.87)
3/4
.824
360
(19.05)
(20.930)
(10.19)
1
1.049
678
(25.4)
(26.645)
(19.19)
1−1/4
1.380
1350
(31.75)
(35.052)
(38.22)
1−1/2
1.610
2090
(38.1)
(40.894)
(59.18)
2
2.067
4020
(50.8)
(52.502)
(113.83)
2−1/2
2.469
6400
(63.5)
(67.713)
(181.22)
3
3.068
11300
(76.2)
(77.927)
(319.98)
NOTE − Capacity given in cubic feet (m
Gas Pipe Capacity − ft
10
20
30
(6.096)
(9.144)
118
95
(3.34)
(2.69)
247
199
(7.00)
(5.63)
466
374
(13.19)
(10.59)
957
768
(27.09)
(22.25)
1430
1150
(40.49)
(32.56)
2760
2220
(78.15)
(62.86)
4400
3530
(124.59)
(99.95)
7780
6250
(220.30)
(176.98)
3
) of gas per hour and based on 0.60 specific gravity gas.
4 − The piping should be sloped 1/4 inch (6.4 mm) per 15
feet (4.57 m) upward toward the meter from the fur-
nace. The piping must be supported at proper intervals
[every 8 to 10 feet (2.44 to 3.01 m)] with suitable hang-
ers or straps. Install a drip leg in vertical pipe runs to the
unit.
5 − A 1/8" N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See figure 35.
6 − In some localities, codes may require the installation of
a manual main shut-off valve and union (furnished by
the installer) external to the unit. The union must be of
the ground joint type.
Compounds used on threaded joints of gas piping
must be resistant to the actions of liquified petro-
leum gases.
NOTE − If emergency shutoff is necessary, shut off the main
manual gas valve and disconnect main power to the fur-
nace. The installer should properly label these devices.
TABLE 9
3
3
/hr (m
/hr)
Length of Pipe − feet (m)
40
50
60
(12.192)
(15.240)
(18.288)
81
72
65
(2.29)
(2.03)
(1.84)
170
151
137
(4.81)
(4.28)
(3.87)
320
284
257
(9.06)
(8.04)
(7.27)
657
583
528
(18.60)
(16.50)
(14.95)
985
873
791
(27.89)
(24.72)
(22.39)
1900
1680
1520
(53.80)
(47.57)
(43.04)
3020
2680
2480
(85.51)
(75.88)
(70.22)
5350
4740
4290
(151.49)
(134.22)
(121.47)
Page 23
IMPORTANT
70
80
90
(21.336)
(24.384)
(27.432)
60
56
52
(1.69)
(1.58)
(1.47)
126
117
110
(3.56)
(3.31)
(3.11)
237
220
207
(6.71)
(6.23)
(5.86)
486
452
424
(13.76)
(12.79)
(12.00)
728
677
635
(20.61)
(19.17)
(17.98)
1400
1300
1220
(39.64)
(36.81)
(34.55)
2230
2080
1950
(63.14)
(58.89)
(55.22)
3950
3670
3450
(111.85)
(103.92)
(97.69)
100
(30.480)
50
(1.42)
104
(2.94)
195
(5.52)
400
(11.33)
600
(17.00)
1160
(32.844)
1840
(52.10)
3260
(92.31)