Remote Controller Wiring - Toshiba MMK-AP0071H Installation Manual

Super modular multi system air conditioner
Hide thumbs Also See for MMK-AP0071H:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 4
Indoor unit power supply
• For the power supply of the indoor unit, prepare the exclusive power supply separated from that of the outdoor unit.
• Arrange the power supply, earth leakage breaker, and main switch of the indoor unit connected to the same
outdoor unit so that they are commonly used.
• Power supply cord specification : Cable 3-core 2.5mm², in conformity with Design 60245 IEC 57.
Indoor/Outdoor inter-unit wiring, Central controller wiring
• 2-core with polarity wires are used for the Indoor/Outdoor inter-unit wiring and Central controller wiring.
• To prevent noise trouble, use 2-core shield wire.
• The length of the communication line means the total length of the inter-unit wire length between indoor and
outdoor units added with the central control system wire length.

Remote controller wiring

• 2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.
Remote controller wiring, remote
controller inter-unit wiring
Total wire length of remote controller
wiring and remote controller inter-unit
wiring = L + L1 + L2 + ... Ln
Total wire length of remote controller inter-unit wiring = L1 + L2 + ... Ln
Indoor unit
Remote
controller
wiring
Remote
controller
Cable connection
• Be sure to pass the cable through the cable connection port of the indoor unit.
• The low-voltage circuit is provided for the remote controller.
• Tighten the screws of the terminal block, and fix the cables
with cord clamp attached to the electric parts box.
(Do not apply tension to the connecting section of the
terminal block.)
Earth line
Connecting
cord
(*1)
(*4)
Twist wire: 0.5mm
In case of wired type only
In case of wireless type included
Indoor unit
L1
Remote controller inter-unit wiring
R
S
(L)
(N)
2
2
to 2.0mm
× 2
Up to 500m
Up to 400m
Up to 200m
Indoor unit
L2
REQUIREMENT
R(L)
Power supply
R(L)
terminal block
2P
Cord clamp
Inter-unit cable between indoor and outdoor units
12
(*2) (*3)
CAUTION
The remote controller wire
(Communication line) and
AC220–240V wires cannot be
parallel to contact each other and
cannot be stored in the same
conduits. If doing so, a trouble
may be caused on the control
system due to noise, etc.
Indoor unit
Ln
(Max. 8 units)
Main P.C. board
S(N)
U1
U2
A
B
X
Y
S(N)
Remote controller
cable
Cord clamp
Power supply cable